Back to smartelemfg Home
Contact us Merchants settle in
Back to smartelemfg Home
Home -Technical

The working principle, function, and setting calculation of zero-sequence voltage protection.

Source: Smartelecmfg 2025-07-04 17:43:05

        Zero-sequence voltage protection is a vital protection scheme in power systems specifically designed for ground faults, particularly single-phase-to-ground faults. It is widely employed in systems with an ungrounded neutral, a neutral grounded via an arc-suppression coil (Petersen coil), or a low-resistance grounded neutral. The following provides a detailed explanation from three aspects: principle, function, and setting calculation.

1. zero-sequence voltage protection Principle
        Zero-sequence voltage (3U₀) is derived from the phasor sum of three-phase voltages:3U₀ = U_A + U_B + U_C
        Normally balanced system: Phasor sum ≈ 0 (3U₀ ≈ 0).
        Ground fault: Voltage collapse in faulted phase generates substantial 3U₀ (3U₀ > 0).

Measurement methods:
        Dedicated zero-sequence VT: Broken-delta connection of three-phase VTs directly outputs 3U₀.
        Digital calculation: Protection relays compute 3U₀ via algorithms.

Physical significance:
        3U₀ is a sensitive indicator of ground faults, especially in:
        Ungrounded (IT) systems
        Resonant-grounded (arc-suppression coil) systems
        High-resistance grounded systems.

2. zero-sequence voltage protection Functions (IEEE C37.2 Device Function 59N)
1).Ground fault detection
        High-sensitivity detection of single-line-to-ground (SLG) and double-line-to-ground (DLG) faults.
        Critical for high-impedance ground faults (e.g., tree contact, cable degradation) where zero-sequence current (3I₀) protection may fail.

2).Backup protection
        Provides backup tripping when 50N/51N (zero-sequence current) protection fails.

3).Insulation monitoring
        Continuous 3U₀ supervision warns of insulation deterioration (e.g., VT failure, intermittent grounding).

4).Directional discrimination aid
        Enables fault directionality (bus vs. line) with directional element 67N.

3.zero-sequence voltage protection Functions Setting Calculations (IEC 60255 Series)
        Settings follow dependability, security, and selectivity principles:

(1) Pickup Setting (U₀>)
        Base value: Normal system unbalance voltage (typically < 1–3% V_ph)
Formula:U₀> = K_rel × U_unb_max
        K_rel: Reliability factor (1.5–2.5, covering transients/harmonics).
        U_unb_max: Maximum measured unbalance voltage.

Typical ranges:
        Effectively grounded systems: 5–10% V_ph
        Non-effectively grounded systems: 10–30% V_ph
        Example: 10kV ungrounded system (V_ph = 5.77 kV), U_unb_max = 0.5% V_ph = 29 V, K_rel=2.0 → U₀> = 58 V (≈1% V_ph).

(2) Time Delay (T)
Purpose: Immunity against transients (switching/lightning) and coordination.

Setting rules:
        Selectivity: Time grading with downstream protection (Δt = 0.3–0.5 s).
        Instantaneous element: Only used with secure VT failure blocking (t ≈ 0.1 s).

Non-effectively grounded systems:
        Alarm stage: 0.5–1.0 s
        Trip stage: 1.0–5.0 s

(3) Sensitivity Verification
        Verify for minimum fault at protection boundary:
        K_sen = U₀_min / U₀> ≥ 1.5
        U₀_min: Minimum 3U₀ at relay location for metallic fault at remote end (calculated via system modeling).

Critical Application Notes
1).VT failure blocking (Device 60FL):
        Mandatory to prevent maloperation (3U₀ may reach 33% V_ph during VT failure).

2).Harmonic immunity:
        Use filters with >20 attenuation ratio for 3rd harmonics (e.g., transformer inrush).

3).Grounding system adaptation:
        Ungrounded systems: Primary protection.
        Effectively grounded systems: Supplemental to 50N/51N (high-impedance faults).

International Standards References:
        IEC 60255-151: Measuring relays functional requirements
        IEEE C37.95: Guide for protective relay applications to power transformers
        IEEE Std C37.100.1: Standard for protective relay terminology
        IEC 61869: Instrument transformer standards

        Zero-sequence voltage protection (59N) provides critical ground fault detection security in non-effectively grounded systems and enhances high-resistance fault coverage in all networks when properly set per international standards.

        Both our line protection relays and transformer protection relays feature zero-sequence voltage protection. Feel free to inquire for procurement!

Product recommendations More
GWZC-9586 Low-voltage generator protection relay
detail
GWZC-9605 Cable insulation monitoring device (IMD)​​(ANSI 64)
detail
GOWE-9000 Partial discharge online monitoring system
detail
GOWE-9000 Wireless Temperature Monitoring System for Substations
detail
GWZC-9604 Feeder Arc Flash Protection Relay
detail
Technical More
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
Main Transformer-Protection Panel
Transformer Protection Relay Panel:Composition and Function
Transformer Protection Relay Panel is primarily used in automation systems for substations and distribution stations in power systems of 11kV, 33kV, 132kV and above. Its main function is to ensure that the transformer can promptly trip the faulty circuit in case of overload, short circuit, gas relay activation, and other abnormal operating conditions, thereby protecting the main transformer from damage and preventing the expansion of faults.
2025/11/24
Feeder Protection Relay
Common Protection Functions for Feeder Protection Relays?
Feeder protection relays are a type of line protection relay and serve as critical devices in distribution systems for protecting power cables (feeders). They integrate multiple protection functions to achieve comprehensive, reliable, and selective protection. Below are the commonly used protection functions of feeder protection relays, along with their corresponding ANSI codes.
2025/11/14
Transformer protection relay
Transformer Differential Protection(ANSI 87T): Working Principle, Function, and Setting Calculation
The working principle of the Transformer Differential Protection Relay is based on Kirchhoff's Current Law. This law states that the sum of currents entering a node is zero. Ideally, for a healthy (non-faulted) transformer, the current entering the primary winding should equal the current leaving the secondary winding (after accounting for the transformer's turns ratio and phase shift).
2025/11/12
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my