Back to smartelemfg Home
Contact us Merchants settle in
Back to smartelemfg Home
Home -Technical

What Are Positive Sequence, Negative Sequence, and Zero Sequence in Three-Phase Circuits?

Source: Maxwell He 2025-08-08 19:02:31

       In relay protection systems, we often encounter concepts such as zero-sequence current protection in microprocessor-based protection relay and inverse-time negative-sequence protection in transformer protection relays. Initially, I found these concepts quite confusing. However, to facilitate subsequent study and work, it is essential to understand these critical concepts of positive sequence, negative sequence, and zero sequence in three-phase circuits.

​Positive Sequence in Three-Phase Circuits​

Definition: Three-phase voltages or currents have equal magnitudes with phase angles successively lagging by 120°, following the sequence A→B→C (clockwise).
Characteristics:

  • Represents the component under normal symmetrical operation.
  • Positive sequence impedance determines symmetrical short-circuit currents (e.g., three-phase faults).

​Example:

  • U A =U∠0°,
  • U B =U∠−120°,
  • U C =U∠120°.

​Negative Sequence in Three-Phase Circuits​

​Definition: Three-phase magnitudes are equal, but phase angles successively lead by 120°, following the sequence A→C→B (counterclockwise).
​Characteristics:

  • Caused by asymmetrical faults (e.g., line-to-line faults, open-phase conditions) or load imbalance.
  • Negative sequence currents can lead to motor overheating and vibration.

​Example:

  • U A =U∠0°,
  • U B =U∠120°,
  • U C =U∠−120°.

​Zero Sequence in Three-Phase Circuits​

​Definition: Three-phase voltages or currents have identical magnitudes and phases (no phase difference).
​Characteristics:

  • Generated by ground faults (e.g., single-line-to-ground) or asymmetrical three-phase conditions.
  • Zero-sequence currents require a neutral wire or earth to form a closed loop.
  • Zero-sequence protection in microprocessor-based protection devices is used to detect ground faults.

Example:

  • U A =U B =U C =U∠0°.

​Mathematical Representation of Positive, Negative, and Zero Sequences (Symmetrical Components Method)​​

Asymmetrical three-phase quantities (U A ,U B ,U C ) can be decomposed into:

  • U 0 = 1/3 (U A +U B +U C ) Zero Sequence
  • U 1 =1/3 (U A +aU B +a 2 U C ) Positive Sequence
  • U 2 =1/3(U A +a 2 U B +aU C )Negative Sequence

where a=e j120° is the phase rotation operator.

​Application Scenarios of Positive, Negative, and Zero Sequences​

  • ​Fault Analysis: Distinguishing fault types (e.g., positive sequence dominates three-phase faults, zero sequence dominates ground faults).
  • Protection Design: Negative sequence protection prevents motor damage; zero sequence protection detects ground faults.
  • ​Imbalance Mitigation: Compensating negative/zero sequence components improves power quality.

​Summary of Positive, Negative, and Zero Sequences​

  • ​Positive Sequence: Symmetrical component under normal operation.
  • ​Negative Sequence: Asymmetrical or reverse-rotating component, harmful to equipment.
  • ​Zero Sequence: In-phase component, indicating ground faults or neutral point displacement.
Product recommendations More
GWZC-9586 Low-voltage generator protection relay
detail
GWZC-9605 Cable insulation monitoring device (IMD)​​(ANSI 64)
detail
GOWE-9000 Partial discharge online monitoring system
detail
GOWE-9000 Wireless Temperature Monitoring System for Substations
detail
GWZC-9604 Feeder Arc Flash Protection Relay
detail
Technical More
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
Main Transformer-Protection Panel
Transformer Protection Relay Panel:Composition and Function
Transformer Protection Relay Panel is primarily used in automation systems for substations and distribution stations in power systems of 11kV, 33kV, 132kV and above. Its main function is to ensure that the transformer can promptly trip the faulty circuit in case of overload, short circuit, gas relay activation, and other abnormal operating conditions, thereby protecting the main transformer from damage and preventing the expansion of faults.
2025/11/24
Feeder Protection Relay
Common Protection Functions for Feeder Protection Relays?
Feeder protection relays are a type of line protection relay and serve as critical devices in distribution systems for protecting power cables (feeders). They integrate multiple protection functions to achieve comprehensive, reliable, and selective protection. Below are the commonly used protection functions of feeder protection relays, along with their corresponding ANSI codes.
2025/11/14
Transformer protection relay
Transformer Differential Protection(ANSI 87T): Working Principle, Function, and Setting Calculation
The working principle of the Transformer Differential Protection Relay is based on Kirchhoff's Current Law. This law states that the sum of currents entering a node is zero. Ideally, for a healthy (non-faulted) transformer, the current entering the primary winding should equal the current leaving the secondary winding (after accounting for the transformer's turns ratio and phase shift).
2025/11/12
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my