Back to smartelemfg Home
Contact us Merchants settle in
Back to smartelemfg Home
Home -Technical

Difference Between Overcurrent Protection and Overload Protection

Source: Maxwell He 2025-08-26 15:51:12

1. Definition and Core Objectives of Overcurrent Protection and Overload Protection

          Overcurrent protection refers to mechanisms that quickly cut off power when current exceeds rated values (regardless of duration), targeting short-term, high-intensity faults like short circuits—this is “strong fault protection.” In contrast, overload protection is designed to disconnect power when current remains slightly above rated values for extended periods, preventing damage from continuous heat accumulation due to long-term overloading—this is “weak fault protection.”

2. Trigger Conditions of Overcurrent Protection and Overload Protection

          Overcurrent protection activates at currents far exceeding rated values (e.g., several to dozens of times higher) with rapid rising rates, even if the overcurrent lasts only milliseconds. Overload protection, however, triggers at currents marginally above rated values (typically 1.1–1.5 times) but requires sustained duration (minutes to tens of minutes). It accounts for thermal accumulation, avoiding false trips from temporary surges like motor startup currents.

3. Action Characteristics of Overcurrent Protection and Overload Protection

          Overcurrent protection features short action times (milliseconds to seconds) with fixed or inverse-time delay (faster for higher currents). It protects main circuits broadly, acting as a “system-level strong safeguard.” Overload protection has longer action times (minutes to tens of minutes) and strictly follows inverse-time characteristics, prioritizing thermal accumulation. It focuses on long-term loaded equipment, serving as “device-level gentle protection.”

4. Applications of Overcurrent Protection and Overload Protection

          Overcurrent protection is used in scenarios with potential short circuits or severe faults, such as main protection for power lines (e.g., feeder circuit breaker instantaneous tripping), transformer/generator differential protection, and motor short-circuit protection (e.g., circuit breaker instantaneous release). Overload protection applies to long-term overloaded equipment, including motor overcurrent protection (e.g., thermal relay long-term overload action), electric heating devices (e.g., temperature/current-linked protection), and lighting line overload protection (e.g., air conditioner thermal-magnetic trip units).

5. Typical Protection Devices for Overcurrent Protection and Overload Protection

          Overcurrent protection primarily uses electromagnetic trip units (e.g., circuit breaker instantaneous trips) or fuses (fast-melting when current exceeds ratings). Overload protection relies on bimetallic thermal Protection relays (utilizing differential expansion of two metals under heat) or electronic overload Protection relays (calculating thermal accumulation via current sampling).

Product recommendations More
GOWE-9000 Partial discharge online monitoring system
detail
GOWE-9000 Wireless Temperature Monitoring System for Substations
detail
GWZC-9604 Feeder Arc Flash Protection Relay
detail
GWZC-9804 Arc Flash Protection Relay
detail
GWZC-9000 Busbar Protection Panel
detail
Technical More
Generator Rotor Single-Point Grounding Protection
Working Principle, Function, and Setting Value Calculation of Generator Rotor Single-Point Grounding Protection (64F)
The core principle of rotor earth fault protection is to monitor the insulation condition of the generator's field circuit (rotor circuit) to ground. Under normal conditions, the rotor circuit is insulated from ground, with only a very small leakage current to earth. A single earth fault does not create a short-circuit path (as a return path is missing), but it serves as a critical alarm because a subsequent second earth fault would have severe consequences.
2025/10/17
GWZC-9000-Hydropower-Plant-Automation-System
Composition of a Hydropower Plant Integrated Automation System
       The main components of a hydropower plant integrated automation system are as follows: 1. Station Level / Control and Monitoring Level This is the "brain" of the entire system, located in the central control room, responsible for plant-wide supervision, control, management, and communication.
2025/10/17
Generator-Comprehensive-Protection-Relay
Protection Functions for Protection Relays of Large Diesel Generators (1000-2000KW)
 The protection system for large diesel generators (1000-2000KW) shall be equipped with the following protection functions:         Overcurrent Protection (ANSI 50/51): Prevents damage to the generator set caused by overload or short circuit.        Overvoltage Protection (ANSI 59): Protects the windings and insulation of the generator set from damage caused by overvoltage.        Undervoltage Protection (ANSI 27): Ensures the generator set trips in a timely manner when the voltage is too low to avoid equipm
2025/10/14
Wireless Temperature Monitoring System for Substations
Wireless Temperature Monitoring System: Application in Switchgear​
This article introduces the application of wireless temperature monitoring systems in high-voltage and low-voltage switchgear. The configuration of the wireless temperature monitoring system varies across different equipment. If you need a customized wireless temperature monitoring solution for your project, please visit our website for more information.
2025/09/08
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my