Applicable Scope :The GWZC-9790N Reverse Power Protection Relay prevents reverse power flow in electrical systems by tripping the circuit upon detection. Used in 6.6kV-33kV systems, it safeguards generators and grid-tied networks with adjustable trip settings. Installed in switchgear panels, it ensures stable operation in power plants and industrial facilities.
Product functions(ANSI):50 | 51 | 49 | 50N/51N | 32 | 32R | 79 | 59 | 27 | 59N | 74
Communication functions :Supported Protocols : IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
Interfaces:2× Ethernet Ports (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports (ANSI/TIA-485-A standard, galvanically isolated)
Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function
Product Introduction :
The GWZC-9790N Reverse Power Protection Relay is a specialized protection device designed to detect and prevent reverse power flow in electrical systems, ensuring safe and stable operation. It monitors active power direction and trips the circuit breaker if power flows in reverse—such as from a generator back into the grid—preventing equipment damage. With adjustable trip thresholds and time delays,
The GWZC-9790N Reverse Power Protection Relay is commonly installed in switchgear panels or protection relay cabinets near generators, transformers, or tie lines in medium-voltage (6.6kV–33kV) power systems. Ideal for generator protection, grid-tied systems, and industrial power networks, this relay enhances reliability in applications like backup power and renewable energy integration.
Product functionsANSI):
1.Instantaneous Overcurrent Protection (ANSI 50)
2.Time-delayed Overcurrent Protection (ANSI 51)
3.Backup Time-delayed Overcurrent Protection (ANSI 51)
4.Overload Protection (ANSI 49)
5.Residual Overcurrent Protection (ANSI 50N/51N)
6.Reverse Power Protection (ANSI 32)
7.Power Restoration (ANSI 32R)
8.Automatic Closing on Power-up (ANSI 79)
9.Overvoltage Protection (ANSI 59)
10.Undervoltage Protection (ANSI 27)
11.Residual Overvoltage Protection (ANSI 59N)
12.Control Circuit Supervision (ANSI 74)
Electrical Specifications
Power Supply:
● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)
Rated AC Parameters:
● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz
Overload Capacity:
● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous
Power Consumption:
● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase
Digital Output:
● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations
Protection Performance
Operating Range:
● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s
Accuracy:
● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%
Trip Time:
● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms
Measurement & Monitoring
Range:
● Voltage: 0.5-120V | Current: 0.02-1.2×In
Accuracy:
● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms
Event Recording:
● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)
Environmental & Mechanical
Operating Temp:
● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*
Storage Temp: -40°C to +80°C
Humidity: 5-90% RH (non-condensing)
Pressure: 60-110 kPa
Compliance:
● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)