GWZC-9601 Fault Islanding Protection Device
Fault Islanding Protection Device Side View
Fault Islanding Protection Device Rear View
GWZC-9601 Fault Islanding Protection Device
Fault Islanding Protection Device Side View
Fault Islanding Protection Device Rear View
GWZC-9601 Fault Islanding Protection Device

Applicable Scope :The ​GWZC-9601 Fault Disconnection Relay​ provides protection for ​10kV-35kV distribution networks, ​microgrids, and ​renewable energy systems​ by detecting and isolating faults (overcurrent, under-voltage, frequency deviations) to prevent cascading failures. Installed in ​substation switchgear​ or ​grid interconnection points, it enables selective fault isolation while maintaining power supply stability.

Product functions(ANSI):59N | 27 | 59 | 81U | 81O | 78 | 60 | 94

Communication functions :Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction :

          The ​GWZC-9601 Fault Disconnection Relay​ is a specialized protection device designed for ​10kV–35kV distribution networks, ​renewable energy integration points, and ​microgrid systems, where rapid fault isolation is critical to prevent cascading failures and maintain grid stability. It detects and isolates faults (such as overcurrent, under-voltage, or frequency deviations) while supporting automatic or manual system separation to protect critical loads.

          The ​GWZC-9601 Fault Disconnection Relay Typically installed in ​distribution substation switchgear cabinets​ or at ​tie points between grid sections, this relay ensures selective fault isolation while preserving power supply continuity in unaffected areas.

Product functionsANSI):

1.Two-stage Zero-sequence Overvoltage Islanding (ANSI 59N)
2.Two-stage Undervoltage Islanding (ANSI 27)
3.Two-stage Bus Overvoltage Islanding (ANSI 59)
4.Two-stage Underfrequency Islanding (ANSI 81U)
5.Two-stage Overfrequency Islanding (ANSI 81O)
6.Out-of-step Islanding (ANSI 78)
7.Potential Transformer Fuse Failure (ANSI 60)
8.External Trip 1/2 (ANSI 94)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

Related products More
GWZC-9602 Anti-islanding protection relay(AIP)
GWZC-9602 Anti-islanding protection relay
detail
GWZC-9603 Reverse Power Protection Relay (ANSI 32)
GWZC-9603 Reverse Power Protection Relay
detail
GWZC-9694 Low-Frequency Low-Voltage Load Shedding Device
GWZC-9694 Low-Frequency Low-Voltage Load Shedding Device
detail
GWZC-9581 Low-voltage generator protection relay
GWZC-9586 Low-voltage generator protection relay
detail
GWZC-9506 Cable insulation monitoring device (IMD)​​(ANSI 64)
GWZC-9506 Cable insulation monitoring device
detail
Technical Knowledge More
Transformer Protection Relay Panel
Renovation Scheme for Unattended Automatic System of Hydropower Station
The core of the transformation of the unattended automation system for hydropower stations is to upgrade the traditional manually attended power station into a modern intelligent power station with "unattended operation and minimal personnel on duty" through computerized monitoring, intelligent sensing, reliable communication and remote centralized control. It realizes remote monitoring, automatic control, fault self-diagnosis and safety early warning, greatly reducing labor costs and improving operational efficiency and safety. Among them, the secondary electrical system, as the "nervous system, brain and safety line of defense" of the power station, is the core support for the unattended transformation. Without a reliable secondary system, true unattended operation cannot be achieved. Therefore, this integration will focus on improving the detailed content of secondary electrical equipment while retaining the full process details of the transformation.
2026/04/21
Ground Distance Protection (21G)
Differences Between Phase-to-Phase Distance Protection (21P) and Ground Distance Protection (21G)
The core difference between phase-to-phase distance protection and ground distance protection lies in the selection of measured quantities, fault response range, and connection methods. They complement each other to form a complete distance protection system for high-voltage transmission lines, both following the basic principle: operation if the measured impedance is less than the setting impedance.
2026/03/04
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
GWZC-9601 Fault Islanding Protection Device
Fault Islanding Protection Device Side View
Fault Islanding Protection Device Rear View
Inquiry Consultation
产品表单
code img
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my