GWZC-9605 Public Measurement and Control Device
Public Measurement and Control Device Side View
Public Measurement and Control Device  Rear View
GWZC-9605 Public Measurement and Control Device
Public Measurement and Control Device Side View
Public Measurement and Control Device  Rear View
GWZC-9605 Public Measurement and Control Device

Applicable Scope :The ​GWZC-9605​ is a multifunctional protection and control relay for ​35kV and below substations, providing ​measurement, switching, communication (IEC 61850/Modbus), and fault recording. Installed in ​switchgear or control panels, it ensures reliable automation in ​distribution networks and industrial plants.

Product functions(ANSI):25 | 51N | 59N

Communication functions :Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction :
          The ​GWZC-9605 Public Measurement and Control Device​ is a versatile protection and automation relay designed for ​35kV and below substations, offering ​measurement, control, communication, and fault recording​ functions. It supports ​IEC 61850 and Modbus protocols​ for seamless SCADA integration and is typically installed in ​switchgear cabinets or control panels​ within ​distribution stations, industrial plants, and renewable energy systems, ensuring reliable monitoring and efficient power management.

Product functionsANSI):

1.Synchronism Check (ANSI 25)
2.Residual Overcurrent Alarm (ANSI 51N)
3.Residual Overvoltage Alarm (ANSI 59N)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

Related products More
GWZC-9506 Cable insulation monitoring device (IMD)​​(ANSI 64)
GWZC-9506 Cable insulation monitoring device
detail
GWZC-9505 Feeder Arc Flash Protection Relay
GWZC-9505 Feeder Arc Flash Protection Relay
detail
GWZC-9605 Arc Flash Protection Relay
GWZC-9605 Arc Flash Protection Relay
detail
GWZC-980​3 Automatic Synchronizing Device (ASD)​
GWZC-980​3 Automatic Synchronizing Device (ASD)​
detail
GWZC-9802 Directional Earth Fault Relay (DEF Relay)
GWZC-9802 Directional Earth Fault Relay
detail
Technical Knowledge More
Transformer Protection Relay Panel
Renovation Scheme for Unattended Automatic System of Hydropower Station
The core of the transformation of the unattended automation system for hydropower stations is to upgrade the traditional manually attended power station into a modern intelligent power station with "unattended operation and minimal personnel on duty" through computerized monitoring, intelligent sensing, reliable communication and remote centralized control. It realizes remote monitoring, automatic control, fault self-diagnosis and safety early warning, greatly reducing labor costs and improving operational efficiency and safety. Among them, the secondary electrical system, as the "nervous system, brain and safety line of defense" of the power station, is the core support for the unattended transformation. Without a reliable secondary system, true unattended operation cannot be achieved. Therefore, this integration will focus on improving the detailed content of secondary electrical equipment while retaining the full process details of the transformation.
2026/04/21
Ground Distance Protection (21G)
Differences Between Phase-to-Phase Distance Protection (21P) and Ground Distance Protection (21G)
The core difference between phase-to-phase distance protection and ground distance protection lies in the selection of measured quantities, fault response range, and connection methods. They complement each other to form a complete distance protection system for high-voltage transmission lines, both following the basic principle: operation if the measured impedance is less than the setting impedance.
2026/03/04
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
GWZC-9605 Public Measurement and Control Device
Public Measurement and Control Device Side View
Public Measurement and Control Device  Rear View
Inquiry Consultation
产品表单
code img
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my