Distributed Solar PV Grid Connection Standards & Voltage Levels Worldwide

Source: SMARTELECMFG 2025-06-11 10:23:10

1. North America (IEEE Standard System)
Grid-Connection Voltage Levels
Low Voltage (LV) Connection
        Single-Phase Systems: 120 V (phase-to-neutral) / 240 V (phase-to-phase), compliant with NEC Article 690.
        Three-Phase Systems: 208Y/120 V (wye-connected), 480 V (delta-connected), with a typical commercial system limit of 1 MVA.
        Standards: IEEE 1547-2018 (interconnection), UL 1741 (inverter certification).

Medium Voltage (MV) Connection
        Typical Voltages: 4.16 kV (delta), 12.47 kV/13.2 kV (wye), 34.5 kV (sub-transmission).
        Capacity Threshold: Most states require systems >1 MVA to connect to MV distribution (per Utility Tariff).

Key Technical Requirements
        Anti-Islanding Protection: Must comply with IEEE 1547-2018 Unintentional Islanding requirements.
        Voltage Regulation: Point of common coupling (PCC) voltage must adhere to ANSI C84.1 (±5% of nominal).


2. Europe (IEC Standard System)
Grid-Connection Voltage Levels
        LV Connection (IEC 60364/EN 50438)
        Three-Phase Systems: 400 V (phase-to-phase, 50 Hz), single-phase 230 V (phase-to-neutral).

Capacity Limits:
        Germany: ≤30 kVA under VDE-AR-N 4105.
        France: ≤36 kVA (three-phase) per EN 50549-1.

MV Connection
        Voltage Levels: 10 kV, 20 kV (IEC 60038), with 22 kV in some Nordic countries.
        Grid Code Compliance: Must meet ENTSO-E Network Code for Requirements for Generators (RfG).

Core Standards
        Harmonic Distortion: THDv <3% (IEC 61000-3-6).
        Fault Ride-Through: LVRT capability per EU Regulation 2016/631.


3. Australia/New Zealand (AS/NZS Standards)
Grid-Connection Voltage Levels
        LV Connection (AS/NZS 4777.2)
        Voltage: 230/400 V (3P4W), with single-phase ≤10 kVA, three-phase ≤30 kVA (DNSP approval required).

MV Connection
        Voltage Levels: 11 kV (urban distribution), 22 kV (rural distribution).

Special Requirements
        Frequency Response: Inverters must support 57–52 Hz range (AS/NZS 4777.1).
        DC Injection: <0.5% rated output current (AS/NZS 4777.2 Clause 5.5.3).


4. Japan (JIS/IEC Hybrid Standards)
Grid-Connection Voltage Levels
        LV Connection (JIS C 8960)
        Single-Phase: 100 V (legacy)/200 V (modern, phase-to-phase).
        Three-Phase: 200 V (delta-connected), ≤50 kW.
High Voltage (HV) Connection
        Voltage Levels: 6.6 kV (standard distribution voltage, JEC-2300).

Key Technologies
        Reverse Power Flow Control: Systems >50 kW require Reverse Power Flow Relay (JEAC 9701).
        Voltage Regulation: PCC voltage ≤101% nominal (JET C0).


5. Other Key Regions
India (IS/IEC Standards)
        LV: 415 V (3P4W), 240 V (1P2W), ≤10 kW (CEA Regulation 2020).
        MV: 11 kV (distribution), 33 kV (primary distribution), per IS 16169 harmonics.

Brazil (NBR/IEC Standards)
        LV: 127 V/220 V (1P), 220 V/380 V (3P), ≤75 kW (ANEEL REN 482).
        MV: 13.8 kV (wye), 34.5 kV (sub-transmission).


International Standards Comparison

International Standards Comparison

Engineering Notes
Terminology Precision:
        Specify connection type (e.g., “208Y/120 V” instead of “208V”).
        Distinguish distribution voltage (e.g., 11 kV) from sub-transmission voltage (e.g., 34.5 kV).

Standard Hierarchy:
        National codes (e.g., VDE) > Regional (EN) > International (IEC).

Emerging Trends:
        Dynamic Voltage Restorers (DVR) in MV systems (IEEE 1547-2022).
        400V DC microgrids in Europe (IEC 62898-2).

        Data Sources: IEC 60038 (standard voltages), latest grid regulations (as of Q1 2024). For country-specific details (e.g., South Africa NRS 097-2), further information can be provided.

Product recommendations More
FZN25-12 series load switchgear
detail
KYN61-40.5 withdrawable AC metal-enclosed high-voltage switchgear
detail
XGN17-40.5 fixed-type high-voltage switchgear
detail
High Voltage Shore Connection Cabinet
detail
Marine Medium/High Voltage Switchboard
detail
Technical More
Gas-Insulated Switchgear (GIS)
Gas-Insulated Switchgear (GIS) for High-Altitude Applications
For Gas-Insulated Switchgear (GIS), since the main live circuits are enclosed within sealed, gas-filled compartments and external connections utilize solid insulation, the insulation performance is unaffected by atmospheric pressure. The primary consideration for GIS at high altitudes is the mechanical strength of the gas enclosure (gas compartment).
2025/08/08
switchgear
What are the differences between IEC-standard switchgear and UL-standard switchgear?
IEC standard switchgear and UL standard switchgear (represented by UL1558 and UL891) fall under different technical systems in power systems, with differences mainly reflected in their standard frameworks, structural design, performance requirements, and applicable scenarios. The following is a comprehensive comparative analysis:
2025/08/08
Ring Main Unit
Technical Requirements and Specifications for 17.5kV Ring Main Units in the Saudi National Grid
SEC Specifications: 17.5kV Ring Main Unit (RMU) - Key Features         Outdoor Enclosure: Designed for outdoor installation.         Dedicated Cable Withstand Voltage Test Terminal Compartment: Features a separate, accessible compartment for cable high-potential (Hi-Pot) testing.         Self-Powered Protection Unit: Utilizes an internal power source for the protection relay.         SF6 Insulated, Single-Tank Design F+F+V Configuration: Common SF6 gas tank housing a combination of Load Switch (F) + Load Switch (F) + Circuit Breaker (V).         Ratings: Ring Switch Unit: 630A. Feeder Circuit Breaker: 200A.         Compliance Standard: SEC Standard 32-SDMS-11.
2025/08/08
Medium Voltage Switchgear
Medium Voltage Switchgear UL Standard Specifications
Switchgear destined for the North American market requires UL (Underwriters Laboratories) certification. UL is a U.S. safety certification organization. It develops its own standards, such as UL 891 (Dead-Front Distribution Switchboards), UL 67 (Panelboards), and UL 845 (Motor Control Centers), and also provides product certification services.
2025/08/07
Inquiry Consultation
+86-13655813785
+86-13655813785
+86-13655813785
+86-13655813785
home product email
live chat
my