XGN17-40.5 fixed-type high-voltage switchgear
XGN17-40.5 fixed-type high-voltage switchgear
XGN17-40.5 fixed-type high-voltage switchgear

Scope of Application:The XGN17-40.5 fixed-type high-voltage switchgear  is a fixed-type, indoor, three-phase AC 50Hz metal-enclosed high-voltage switchgear. Designed for 40.5kV power networks (equivalent to the IEC 36kV system level), it is used in power plants, substations, industrial facilities, and large building distribution systems. Its core functions include power reception, distribution, control, protection, and monitoring. Supporting single-bus or single-bus with bypass configurations, it is engineered for high-reliability applications requiring frequent operations.

Rated Voltage: 33KV,34.5KV,35KV,36KV
Rated Current: Main bus 1250A/1600A/2000A/2500A; Feeder bus 630A/1250A/1600A/2000A
Short-Circuit Parameters: Rated short-circuit breaking current 25kA/31.5kA; Rated short-circuit making current (peak) 63kA/80kA; Rated short-time withstand current (4s) 25kA/31.5kA; Rated peak withstand current 63kA/80kA
Insulation Parameters: Power frequency withstand voltage 95kV (1min); Lightning impulse withstand voltage 185kV
Control Supply: DC 24V/48V/110V/220V; AC 110V/220V

Product Introduction Technical Parameter Size

1.Product Overview
        The XGN17-40.5 features a metal-enclosed, fixed-compartment structure compliant with GB3906 and IEC 60298 standards. Utilizing air insulation (minimum clearance ≥300mm), its welded steel frame divides into front compartment (operation zone) and rear compartment (cable/bypass zone). Compatible with vacuum circuit breakers (e.g., ZN12-35) or SF₆ circuit breakers (e.g., FP series), it supports bus sectioning and bypass schemes for flexible power distribution. Key design objectives include full-load operation capability, high mechanical endurance (>10,000 operations), and minimal maintenance.

2.Product Functions
Core Functions:
        Power Distribution: Distributes 40.5kV power via main and feeder bus systems.
        Circuit Control: Enables manual/electric switching with remote operation option.
        System Protection: Integrates overcurrent/short-circuit protection (through circuit breakers and relays) with breaking capacity up to 31.5kA.
        Operational Monitoring: Equipped with metering compartment for real-time voltage/current/power measurement (some models feature communication interfaces).

Ancillary Functions:
        Five-Prevention Interlocking: Mechanical interlocks prevent misoperations (e.g., switching under load).
        Bypass Supply: Enables maintenance without interruption via bypass bus.
        Safety Protection: Automatic insulating shutters shield live contacts; voltage indicators display energization status.

3.Product Composition
Enclosure Structure:
        Front Compartment: Busbar compartment (top), circuit breaker compartment (center), relay compartment (front). Busbar and breaker zones separated by insulated barriers with bushing connections.
        Rear Compartment: Cable compartment, bypass bus zone, and mounting positions for VTs/arresters. Rear door features mechanical locking and live-part blocking.

Key Components:
        Circuit Breaker: Vacuum type (e.g., ZN12-35, 2000A) or SF₆ type (e.g., FP series) for primary circuit interruption.
        Disconnector: Provides visible isolation gap; mechanically interlocked with breaker.
        Instrument Transformers: Current transformers (CTs) for measurement/protection; voltage transformers (VTs) for voltage monitoring.
        Operating Mechanism: Spring-operated, motor/manual charging.
        Protection Relay: Integrates overcurrent/earth fault protection.

Technical Parameters
Electrical Specifications:
        Rated frequency: 50Hz;
        Power frequency withstand voltage: 95kV/1min (main circuit), 118kV/1min (isolation gap);
        Lightning impulse withstand voltage: 185kV (main circuit), 215kV (isolation gap).

Mechanical Specifications:
        Mechanical endurance: >10,000 operations (circuit breaker);
        Operating sequence: O-0.3s-CO-180s-CO (auto-reclosing cycle).

Environmental Compliance:
        Temperature range: -25℃ to +40℃ (extendable to -40℃ with special design);
        Altitude limit: ≤1000m (derating required above);
        Humidity: ≤95% daily average (at +25℃);
        Seismic withstand: Intensity 8.

Model & Dimensions
        Model: Base model XGN17-40.5, with variants (e.g., XGN17C-40.5 for enhanced configuration)
        Dimensions (W×D×H): Standard type ≈1918mm×2950mm×3100mm; Bypass bus type ≈1918mm×3250mm×3125mm or 2020mm×3650mm×3400mm (varies by manufacturer)

Related products More
XGN15-12 Fixed-type Switchgear
XGN15-12 Fixed-type Switchgear
detail
Medium Voltage Automatic Transfer Switchgear(MV ATS)
Medium Voltage Automatic Transfer Switchgear
detail
Low-Voltage Feeder Switchgear
Low-Voltage Feeder Switchgear
detail
FZN25-12 series load switchgear
FZN25-12 series load switchgear
detail
KYN61-40.5 withdrawable AC metal-enclosed high-voltage switchgear
detail
industry news More
XGN17-40.5 fixed-type high-voltage switchgear
Inquiry Consultation
产品表单
code img
Inquiry Consultation
+86-15871108231
+86-15871108231
+86-13655813785
+86-15871108231
home product email
live chat
my