XGN15-12 Fixed-type Switchgear
XGN15-12 Fixed-type Switchgear

Scope of Application:The XGN15-12 is an indoor, air-insulated, metal-enclosed fixed-type switchgear for three-phase AC 50Hz systems, designed for power distribution, circuit protection, and control in substations, industrial plants, and infrastructure networks at 12kV.

Rated Voltage (IEC 62271-200): 15kV,12KV,11KV,10KV,7.2KV,6.6KV
Rated Current: Main circuit: 630A, 1250A, 1600A, 2000A, 2500A, 3150A.
Rated Short-Circuit Breaking Current: 25kA, 31.5kA (1s withstand).
Power Frequency Withstand Voltage: 42kV/1min (Main circuit), 30kV/1min (Auxiliary circuit).
Lightning Impulse Withstand Voltage: 75kV (Peak).
Ingress Protection (IP) Rating (IEC 60529): Enclosure: IP4X, Between compartments: IP2X.

Product Introduction Technical Parameter Size

1. XGN15-12 Fixed-type Switchgear Product Overview
        The XGN15-12 is a metal-enclosed fixed-type switchgear featuring modular design, compliant with IEC 62271-200. The enclosure utilizes a welded cold-rolled steel structure, internally divided into four segregated compartments: circuit-breaker compartment, busbar compartment, cable compartment, and relay/instrument compartment, providing Internal Arc Fault protection (IAC-AFLR Class) via metal partitions. The primary switching device can be a fixed-mounted Vacuum Circuit Breaker (VCB) or SF6 Load Break Switch (LBS). It supports cable terminations, metering, and protection functions, suitable for ring main unit (RMU) and radial feeder applications.

2. XGN15-12 Fixed-type Switchgear Product Functions
        Main Circuit Switching: Load and short-circuit current interruption via Vacuum Circuit Breaker (VCB).
        Protection: Integrated overcurrent, short-circuit, and earth fault protection (when used with Protection relays).
        Isolation & Earthing: Equipped with Disconnector (Isolator) and Earthing Switch (Earth Switch) for safe maintenance.
        Measurement & Monitoring: Provisions for Current Transformers (CTs) and Voltage Transformers (VTs) for metering and condition monitoring.
        Five Safety Interlocking Mechanisms:
        Prevent disconnector operation under load.
        Prevent incorrect circuit-breaker operation.
        Prevent earthing switch closure on energized circuits.
        Prevent circuit energization with earthing switch closed.
        Prevent access to live compartments.

3. XGN15-12 Fixed-type Switchgear Product Features
        High Safety: Type-tested according to IEC 62271-200 with Internal Arc Fault Classification (IAC Class).
        Modular Design: Supports flexible configuration schemes (incoming/outgoing feeder, metering, VT, etc.).
        Maintenance-Free Primary Switch: Vacuum Circuit Breaker utilizes solid-insulated poles (sealed encapsulation), eliminating leakage risks.
        Visual Indication: Mechanical viewing windows for disconnector/earthing switch position.
        Strong Expandability: Can be equipped with SCADA interface for remote monitoring.
        Environmental Compatibility: SF6-free (for VCB version), aligning with green grid initiatives.

XGN15-12 Fixed-type Switchgear Detailed Product Parameters
        Parameter: Specification
        Insulation Medium r: Air
        Rated Frequency r:50Hz
        Main Busbar Current Ratingr: ≤ 3150A
        Branch Busbar Current Ratingr: ≤ 3150A
        Short-Time Withstand Current (3s)r: 25kA, 31.5kA
        Peak Withstand Currentr: 63kA, 80kA
        Mechanical Endurancer: Circuit Breaker: ≥ 10,000 operations; Disconnector/Earthing Switch: ≥ 2,000 operations
        Operating Mechanism r: Spring-operated
        Ambient Temperature Ranger: -15°C to +40°C
        Relative Humidityr: ≤ 95% (daily average), ≤ 90% (monthly average)

XGN15-12 Fixed-type Switchgear Model & Dimensions
       Model Designation: XGN15-12(F)/□
       F: Equipped with Vacuum Circuit Breaker (VCB).
       □: Scheme number (e.g., 01, 21).
       Standard Dimensions (W × D × H): 800/1000mm × 1500mm × 2300mm (Customizable).

Related products More
XGN17-40.5 fixed-type high-voltage switchgear
XGN17-40.5 fixed-type high-voltage switchgear
detail
FZN25-12 series load switchgear
FZN25-12 series load switchgear
detail
KYN61-40.5 withdrawable AC metal-enclosed high-voltage switchgear
detail
High Voltage Shore Connection Cabinet
detail
Marine Medium/High Voltage Switchboard
Marine Medium/High Voltage Switchboard
detail
technical knowledge More
Gas-Insulated Switchgear (GIS)
Gas-Insulated Switchgear (GIS) for High-Altitude Applications
For Gas-Insulated Switchgear (GIS), since the main live circuits are enclosed within sealed, gas-filled compartments and external connections utilize solid insulation, the insulation performance is unaffected by atmospheric pressure. The primary consideration for GIS at high altitudes is the mechanical strength of the gas enclosure (gas compartment).
2025/08/08
switchgear
What are the differences between IEC-standard switchgear and UL-standard switchgear?
IEC standard switchgear and UL standard switchgear (represented by UL1558 and UL891) fall under different technical systems in power systems, with differences mainly reflected in their standard frameworks, structural design, performance requirements, and applicable scenarios. The following is a comprehensive comparative analysis:
2025/08/08
Ring Main Unit
Technical Requirements and Specifications for 17.5kV Ring Main Units in the Saudi National Grid
SEC Specifications: 17.5kV Ring Main Unit (RMU) - Key Features         Outdoor Enclosure: Designed for outdoor installation.         Dedicated Cable Withstand Voltage Test Terminal Compartment: Features a separate, accessible compartment for cable high-potential (Hi-Pot) testing.         Self-Powered Protection Unit: Utilizes an internal power source for the protection relay.         SF6 Insulated, Single-Tank Design F+F+V Configuration: Common SF6 gas tank housing a combination of Load Switch (F) + Load Switch (F) + Circuit Breaker (V).         Ratings: Ring Switch Unit: 630A. Feeder Circuit Breaker: 200A.         Compliance Standard: SEC Standard 32-SDMS-11.
2025/08/08
XGN15-12 Fixed-type Switchgear
Inquiry Consultation
产品表单
Inquiry Consultation
+86-13655813785
+86-13655813785
+86-13655813785
+86-13655813785
home product email
live chat
my