Back to smartelemfg Home
Contact us Merchants settle in
Back to smartelemfg Home
Home -Technical

Generator Loss-of-Excitation Protection

Source: Smartelecmfg 2025-07-08 10:17:34

Introduction to Generator Loss-of-Excitation Protection

          GWZC-9681 Generator Backup Protection Relay features generator loss-of-field protection function. Generator loss-of-excitation protection serves as a critical defense against generator excitation current failure caused by excitation system faults. As vital protection against system oscillations, terminal equipment damage, and reverse flow of reactive power during asynchronous operation.

I. Loss-of-Field Fault Mechanism & Hazards​

​Principle​
          Loss of excitation current → Generator EMF decay → Loss of synchronous torque → Transition to asynchronous operation (slip operation)

          Formula: Synchronous torque T sync∝ X dE f V s sinδ → E f→0 during field loss

​Critical Hazards​
          ​Grid impact: Absorbs reactive power up to 2× rated capacity (risk of voltage collapse)
          ​Generator damage: Rotor overheating (eddy current losses), stator overcurrent (asymmetric torque pulsation), mechanical vibration

II. Protection Operating Criteria (Primary Schemes)​​

Setting Requirements:​


Auxiliary Criteria:​​

          ​​Undervoltage lockout: Enable protection when terminal voltage <80% U n

          ​Negative-sequence blocking: Immunity to asymmetrical faults

III. Standardized Configuration (Example: Pumped Storage Plant)​

IV. Key Maintenance Practices​

​Setting Verification​
          Static tests: Inject 50%-100% rated current to validate impedance boundaries
          Dynamic simulation: RTDS modeling of slip operation (slip ratio S=0.02-0.05)

​False Trip Prevention

Product recommendations More
GWZC-9684 Generator-Transformer Differential Protection Relay (87G|87T)
detail
GWZC-9683 Generator Differential Protection Relay(87G)
detail
GWZC-9682 Generator Rotor Earth Fault Protection Relay
detail
GWZC-9681C Generator Comprehensive Protection Relay
detail
GWZC-9681 Generator Backup Protection Relay
detail
Technical More
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
Generator Protection
Working Principle, Function, and Setting Value Calculation of Generator Rotor Single-Point Grounding Protection (64F)
The core principle of rotor earth fault protection is to monitor the insulation condition of the generator's field circuit (rotor circuit) to ground. Under normal conditions, the rotor circuit is insulated from ground, with only a very small leakage current to earth. A single earth fault does not create a short-circuit path (as a return path is missing), but it serves as a critical alarm because a subsequent second earth fault would have severe consequences.
2025/10/17
Generator Protection
What relay protection functions should be configured for a marine generator?
Generator protection devices must include at least the following core protection functions. Additional functions may be required depending on system configuration (e.g., generator capacity, parallel operation, neutral grounding method): 1.Overcurrent Protection (50/51):           Instantaneous Overcurrent (50): Clears severe phase-to-phase short-circuit faults with extremely fast operation (millisecond level).           Definite Time / Inverse Time Overcurrent (51): Clears remote or moderate overloads and short-circuit faults, providing backup protection. Must coordinate with downstream protection (e.g., feeder breakers) to ensure selectivity. Inverse time characteristics better match equipment thermal withstand capability.           Short-Circuit Backup Protection: Typically provided by overcurrent protection (51), acting as backup to primary protection (e.g., differential).
2025/08/04
generator 100% stator earth fault protection.
Working principle, function, and setting calculation for the generator 100% stator earth fault protection.
Generator 100% stator earth fault protection overcomes traditional coverage limitations by combining two complementary methods. The third-harmonic voltage principle monitors the neutral-to-terminal voltage ratio to detect faults near the neutral, triggering when this ratio falls below a typical threshold of 0.3-0.5. Simultaneously, the low-frequency injection method introduces a 20Hz signal to measure insulation resistance across the entire winding, operating if resistance drops below pre-set thresholds (typically 1-5 kΩ). This dual approach ensures complete stator coverage without dead zones, provides high sensitivity for kΩ-range faults, and offers redundancy. Protection settings are derived from security margins applied to measured normal operating parameters, including harmonic voltage ratios and maximum unbalanced voltage, making it essential for large generator security.
2025/07/07
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my