Back to smartelemfg Home
Contact us Merchants settle in
Back to smartelemfg Home
Home -Technical

Working principle, function, and setting calculation for the generator 100% stator earth fault protection.

Source: Smartelecmfg 2025-07-07 15:26:28

1. Generator 100% Stator Earth Fault Protection Principle
        Traditional stator earth fault protection (e.g., fundamental zero-sequence voltage protection) covers only 80–95% of the stator winding, leaving a dead zone near the neutral point. 100% stator earth fault protection combines dual principles for full coverage:

(1) Third-Harmonic Voltage Principle (Neutral Zone Protection)
        Mechanism: Under normal operation, magnetic field distortion in the air gap generates third-harmonic voltages (U3N at neutral, U3T at terminal). The ratio satisfies:

|U3N|/|U3T|≈1

Fault Response:
        Earth fault near neutral: U3N decreases,increases → Ratio U3T drops significantly.
        Protection Criterion:|U3N|/|U3T|<Kset(Typical setting: Kset=0.3−0.5).

(2) Low-Frequency Injection Principle (20 Hz Injection, Full Coverage)
        Method: Injects a 20 Hz voltage signal via the neutral earthing transformer or dedicated coupler.
Fault Detection:
        Normal: High impedance → Small injection current (Iinj).
        Earth fault: Stator insulation resistance (Rf) drops → Iinj increases.
        Criterion: Monitors Iinj or computes Rf:

Rf=Uinj/Iinj(Trip if Rf<Rset )

2.generator 100% stator earth fault protection Functions
        Full Winding Coverage: Eliminates dead zone (5–20% near neutral), protecting 100% of the stator.
        High Sensitivity : Detects high-resistance faults (up to several kΩ), preventing fault escalation.
        Dual Redundancy : Third-harmonic + injection principles act as mutual backups.
        Backup Protection : Provides backup for 95% stator earth fault protection.

3. generator 100% stator earth fault protection Setting Calculations
(1) Third-Harmonic Voltage Protection
        Ratio Setting:

        Kset=Krel×(|U3N|/|U3T|)min

        Krel: Security margin (1.2–1.5).
        (|U3N|/|U3T|)min: Minimum measured ratio under normal operation (typically 0.5–1.0). 
        Typical Setting: Kset =0.3−0.5.

(2) Low-Frequency Injection Protection
Insulation Resistance Setting:

        Rset= Rins.min/Krel

        Rins.min : Minimum allowable stator insulation resistance (usually 5–10 kΩ).
        Krel: Security margin (1.5–2.0).
        Typical Setting: Rset=1−5kΩ.
Time Delay: 0.5–1.0 s (avoids transient disturbances).

(3) Fundamental Zero-Sequence Voltage Protection (95% Coverage, Coordination)
Setting:

        U0.set=Krel×U0.max

        U 0.max: Maximum unbalanced voltage during normal operation (5–10 V secondary).
        Krel: Security margin (1.3–1.5).
        Typical Setting: U0.set=5−15V (secondary).

Engineering Considerations
        1.Third-Harmonic Scheme Applicability: Performance varies with load/power factor; verify across all operating conditions.
        2.Injection Scheme Advantage: Unaffected by operating state; requires dedicated injection equipment.
        3.Setting Validation: Measure U3N/U3T ratio and fundamental U0 during commissioning.
        4.Coordination: 100% protection delays (0.5–1 s) coordinate with instantaneous 95% protection.

Example Setting Procedure:
        1.Measure:U3N/U3T at no-load/full-load; obtain minimum ratio 0.6.
        2.Set third-harmonic protection: Kset=1.3×0.6=0.48→0.5.
        3.Set injection protection: Rset=3kΩ (per manufacturer).
        4.Set zero-sequence voltage:U0.set=1.3×8V=10.4V→10V

Generator 100% Stator Earth Fault Protection SummaryGenerator 100% Stator Earth Fault Protection Summary

Conclusion: The synergy of third-harmonic monitoring and active low-frequency injection enables dead-zone-free, high-reliability stator earth fault protection, essential for large generators.

Our company’s GWZC-9886 Generator Backup Protection Relay features 100% Stator Ground Protection. Welcome inquiries and procurement!

Product recommendations More
GWZC-9586 Low-voltage generator protection relay
detail
GWZC-9605 Cable insulation monitoring device (IMD)​​(ANSI 64)
detail
GOWE-9000 Partial discharge online monitoring system
detail
GOWE-9000 Wireless Temperature Monitoring System for Substations
detail
GWZC-9604 Feeder Arc Flash Protection Relay
detail
Technical More
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
Main Transformer-Protection Panel
Transformer Protection Relay Panel:Composition and Function
Transformer Protection Relay Panel is primarily used in automation systems for substations and distribution stations in power systems of 11kV, 33kV, 132kV and above. Its main function is to ensure that the transformer can promptly trip the faulty circuit in case of overload, short circuit, gas relay activation, and other abnormal operating conditions, thereby protecting the main transformer from damage and preventing the expansion of faults.
2025/11/24
Feeder Protection Relay
Common Protection Functions for Feeder Protection Relays?
Feeder protection relays are a type of line protection relay and serve as critical devices in distribution systems for protecting power cables (feeders). They integrate multiple protection functions to achieve comprehensive, reliable, and selective protection. Below are the commonly used protection functions of feeder protection relays, along with their corresponding ANSI codes.
2025/11/14
Transformer protection relay
Transformer Differential Protection(ANSI 87T): Working Principle, Function, and Setting Calculation
The working principle of the Transformer Differential Protection Relay is based on Kirchhoff's Current Law. This law states that the sum of currents entering a node is zero. Ideally, for a healthy (non-faulted) transformer, the current entering the primary winding should equal the current leaving the secondary winding (after accounting for the transformer's turns ratio and phase shift).
2025/11/12
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my