Back to smartelemfg Home
Contact us Merchants settle in
Back to smartelemfg Home
Home -Technical

Common Protection Functions for Feeder Protection Relays?

Source: Smartelecmfg 2025-11-14 16:47:06

        Feeder protection relays are a type of line protection relay and serve as critical devices in distribution systems for protecting power cables (feeders). They integrate multiple protection functions to achieve comprehensive, reliable, and selective protection. Below are the commonly used protection functions of feeder protection relays, along with their corresponding ANSI codes.

I. Core Overcurrent Protection Functions
        This is the most fundamental and core part of feeder protection.

1.Instantaneous Overcurrent Protection
        ANSI 50
        Function: Initiates an immediate, time-delay free trip when the current exceeds a very high setpoint (typically used for detecting severe faults like phase-to-phase short circuits). It provides rapid fault clearance but requires coordination with upstream protection.
        Application: Protection against severe faults close to the feeder origin.

2.Definite Time Overcurrent Protection
        ANSI 51
        Function: When the current exceeds a set value (typically lower than the 50 setting), the relay trips after a fixed, pre-defined time delay. This delay is used for time coordination with downstream (e.g., lateral circuits) and upstream (e.g., main transformer) protection.
        Application: Serves as the primary protection for the feeder and backup protection for downstream elements.

3.Inverse Time Overcurrent Protection
        ANSI 51V or 51
        Function: The operating time is inversely proportional to the magnitude of the fault current. Higher fault currents result in shorter operating times. It provides better coordination with equipment damage curves and is often used for protecting motors, transformers, and also applied in feeders.
        Types: Typically follows standard curves such as EI (Extremely Inverse), VI (Very Inverse), MI (Moderately Inverse).

II. Earth Fault Protection
        Used to detect single-phase-to-ground faults, the most common fault type in distribution systems.

1.Instantaneous Earth Fault Protection
        ANSI 50N (for residual current measurement) or 50G (for direct zero-sequence current measurement)
        Function: Similar to the 50 function, but specifically detects earth fault current. Trips instantaneously when the earth fault current exceeds a high setpoint.

2.Definite/Inverse Time Earth Fault Protection
        ANSI 51N (for residual current measurement) or 51G (for direct zero-sequence current measurement)
        Function: Similar to the 51 function, but specifically detects earth fault current. By setting current values and time delays, it enables selective isolation of earth faults.

III. Other Important Protection Functions
        Modern digital Protection relays integrate many advanced protection features.

1.Directional Overcurrent Protection
        ANSI 67 (Phase Directional Overcurrent), 67N (Directional Earth Fault)
        Function: Not only detects overcurrent but also determines the direction of the fault power flow. Operation occurs only if the fault current flows in the specified “forward direction” (typically from the busbar into the line). This is crucial for meshed networks or systems with multiple sources to ensure only the faulted line is disconnected.

2.Autorecloser
        ANSI 79
        Function: Automatically attempts to re-close the circuit breaker after a protection trip. Since most faults on overhead lines are transient (e.g., lightning, wind-blown debris), power supply can be restored after the arc extinguishes. Autoreclosing significantly improves power supply reliability.

3.Under/Overvoltage Protection
        ANSI 27 (Undervoltage), 59 (Overvoltage)
        Function: Monitors system voltage. Operates after a time delay when voltage becomes abnormal (too low or too high), used to protect sensitive equipment or for system separation.

4.Under/Overfrequency Protection
        ANSI 81O/U (Overfrequency/Underfrequency)
        Function: Monitors system frequency. Frequency abnormalities typically indicate generation-load imbalance, often used for islanding detection or protecting generation equipment.

5.Differential Protection
        ANSI 87
        Function: Compares the magnitude and phase of currents at both ends (source and load) of the feeder. Under normal conditions or for external faults, these currents are equal; during an internal fault within the protected zone, a current difference appears, causing the Differential Protection relay to operate rapidly. This is a very fast and sensitive unit protection scheme, but requires a communication channel, typically used for important cable feeders.

        In practical applications, the protection configuration for a specific feeder is selected from combinations of the functions above based on its voltage level, network configuration (radial, meshed), line type (overhead, cable), and criticality. For example, a simple radial overhead feeder might be configured with only 50/51/51N/79, whereas a critical cable feeder in a meshed network might require a more complex scheme like 67/67N/87.

Product recommendations More
GWZC-9611 Feeder Protection Relay
detail
GWZC-9811 Line protection relay
detail
GWZC-9811C Line differential protection relay (87H | 87)
detail
GWZC-9812 Distance protection relay(21 | 21G | 21FL)
detail
GWZC-9913 FO Line Diff Relay(87L)
detail
Technical More
Main Transformer-Protection Panel
Transformer Protection Relay Panel:Composition and Function
Transformer Protection Relay Panel is primarily used in automation systems for substations and distribution stations in power systems of 11kV, 33kV, 132kV and above. Its main function is to ensure that the transformer can promptly trip the faulty circuit in case of overload, short circuit, gas relay activation, and other abnormal operating conditions, thereby protecting the main transformer from damage and preventing the expansion of faults.
2025/11/24
Transformer protection relay
Transformer Differential Protection(ANSI 87T): Working Principle, Function, and Setting Calculation
The working principle of the Transformer Differential Protection Relay is based on Kirchhoff's Current Law. This law states that the sum of currents entering a node is zero. Ideally, for a healthy (non-faulted) transformer, the current entering the primary winding should equal the current leaving the secondary winding (after accounting for the transformer's turns ratio and phase shift).
2025/11/12
Capacitor-protection-relay
Capacitor Unbalance Voltage Protection: Working Principle, Function, and Setting Calculation
Capacitor Unbalance Voltage Protection is used to monitor the voltage distribution among individual units within a capacitor bank, particularly in series-connected banks. Its operating principle is based on Kirchhoff's Voltage Law and capacitor voltage division. Under normal operating conditions, the voltage across each unit in the bank is relatively balanced, resulting in a minimal unbalance voltage. When a capacitor unit fails (e.g., internal short circuit, open circuit, or performance degradation), the voltage distribution becomes unequal, generating a significant unbalance voltage.
2025/11/12
Capacitor-protection-relay
Capacitor Unbalanced Current Protection: Working Principle, Function, and Setting Calculation
Capacitor unbalanced current protection is a critical technology in power systems used to detect and protect against internal faults within capacitor banks. It operates by monitoring the changes in unbalanced current at the neutral point or bridge circuit of the capacitor bank, promptly isolating faults to prevent their escalation.
2025/11/05
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my