GWZC-9886 Generator Backup Protection Relay
Generator Backup Protection Relay Side View
Generator Backup Protection Relay Rear View
GWZC-9886 Generator Backup Protection Relay
Generator Backup Protection Relay Side View
Generator Backup Protection Relay Rear View
GWZC-9886 Generator Backup Protection Relay

Applicable Scope :The ​GWZC-9886​ is a generator backup protection relay for 10kV–35kV systems, providing overcurrent, under/overvoltage, reverse power, and negative sequence protection. Installed in generator panels or switchgear, it ensures backup security during faults or grid disturbances.

Product functions(ANSI):50/51 | 51 | 49 | 46 | 50N/51N | 40 | 32 | 81O/81U | 59/27 | 59N | 64S | 60 | 27 | 27/81U | 74

Communication functions :Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction :
          The ​GWZC-9886 Generator Backup Protection Relay​ is a critical protection device designed for medium to large generators (10kV–35kV) in power plants, hydro stations, and industrial cogeneration systems. It provides backup protection against faults such as overcurrent, under/overvoltage, reverse power, and negative sequence currents, while also monitoring key parameters like voltage, current, power, and frequency.

          GWZC-9886 Generator Backup Protection Relay typically installed in generator protection panels or switchgear cabinets alongside primary relays, the GWZC-9866 ensures redundancy and safeguards generators during grid disturbances, internal faults, or abnormal operating conditions, enhancing overall system reliability.

Product functionsANSI):

1.Three-Step Overcurrent Protection with Voltage Restraint and Memory Overcurrent (ANSI 50/51)
2.Inverse Time Overcurrent Protection (ANSI 51)
3.Overload Protection (ANSI 49)
4.Negative Sequence Overcurrent Protection (ANSI 46)
5.Inverse Time Negative Sequence Overcurrent Protection (ANSI 46)
6.Zero Sequence Overcurrent Protection (ANSI 50N/51N)
7.Loss of Excitation Protection (ANSI 40)
8.Reverse Power Protection (ANSI 32)
9.Frequency Protection (Overfrequency/Underfrequency) (ANSI 81O/81U)
10.​​Voltage Protection (Overvoltage/Undervoltage) (ANSI 59/27)
11.Zero Sequence Overvoltage Protection (Neutral Point Zero Sequence) (ANSI 59N)
12.Third Harmonic Voltage Stator Ground Protection (ANSI 64S)
13.Potential Transformer (PT) Open-Circuit Alarm (ANSI 60)
14.Potential Transformer (PT) Loss of Voltage Alarm (ANSI 27)
​​15.System Power Loss (Alarm/Trip Optional) (ANSI 27/81U)
16.Control Circuit Open-Circuit Alarm (ANSI 74)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

Related products More
GWZC-9885 Generator Rotor Earth Fault Protection Relay
GWZC-9885 Generator Rotor Earth Fault Protection Relay
detail
GWZC-9884 Generator Differential Protection Relay(87H | 87 | 87A)
GWZC-9884 Generator Differential Protection Relay
detail
GWZW-9883 Generator Comprehensive Protection Relay
GWZW-9883  Generator Comprehensive Protection Relay
detail
GWZC-9913 FO Line Diff Relay(87L)
detail
GWZC-9916 Bus differential protection relay
GWZC-9916 Bus differential protection relay
detail
GWZC-9886 Generator Backup Protection Relay
Generator Backup Protection Relay Side View
Generator Backup Protection Relay Rear View
Inquiry Consultation
产品表单
Inquiry Consultation
13655811378
13655811378
13655811378
13655811378
home product email
live chat
my