GWZC-9602 Anti-islanding protection relay(AIP)

Applicable Scope :The ​GWZC-9602 Anti-islanding Protection Relay​ prevents islanding in distributed generation systems (solar, wind, microgrids) with voltage/frequency protection, power monitoring, and communication (IEC 61850/Modbus). Installed in ​switchgear (PCC) or control panels, it ensures safe grid interconnection compliance.

Product functions(ANSI):81O | 81U | 59 | 27 | 81R | 32 | 94 | 67 | 50N/51N | 59N | 79 | 60FL | 50H/51H

Communication functions :Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction  of Anti-islanding Protection Relay

          The ​GWZC-9890D Anti-islanding Protection Relay​ is a specialized device engineered to prevent ​unintentional islanding​ in distributed generation systems (e.g., solar farms, wind turbines, and cogeneration plants). Its core function is to ​detect grid failure​ using active/passive monitoring techniques (measuring voltage, frequency, rate-of-change of frequency, and phase displacement) and ​rapidly disconnect generators​ within milliseconds upon detecting an islanding condition.

          The ​GWZC-9602 Anti-islanding Protection Relay ensures safety for utility personnel, prevents equipment damage, and maintains grid stability. Additionally, it supervises ​grid re-synchronization​ to block reconnection until voltage, frequency, and phase alignment are stable. Typically installed at the ​Point of Common Coupling (PCC)​​ in generator switchgear or substation protection panels (for voltages ≤ 33kV/35kV), it serves as a critical safety device for compliant grid integration of distributed energy resources.

Product functionsANSI):

1.Overfrequency Protection (ANSI 81O)
2.Underfrequency Protection (ANSI 81U)
​3.Overvoltage Protection (ANSI 59)
​4.Undervoltage Protection (ANSI 27)
​5.Rate of Change of Frequency Protection (ANSI 81R)
​6.Reverse Power Protection (ANSI 32)
​7.External Trip (ANSI 94)
​8.​​Directional Overcurrent Protection (ANSI 67)
9.Residual Overcurrent Protection (ANSI 50N/51N)
10.Residual Overvoltage Protection (ANSI 59N)
​11.​Voltage Check Auto-Reclosing (ANSI 79)
​12.Potential Transformer Fuse Failure (ANSI 60FL)
13.Harmonic Detection (ANSI 50H/51H)

Electrical Specifications​

​Power Supply:​​

          ● AC: 85-264V, 47-63Hz (≤15% THD)
          ● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

          ● Voltage: 100V/√3 or 100V
          ● Current: 5A/1A
          ● Frequency: 50Hz

​Overload Capacity:​​

          ● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
          ● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

          ● Supply: <10W (static), ≤15W (trip)
          ● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
          ● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

          ● Dry contact (8A@250VAC / 30VDC)
          ● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
          ● Operating Time: 5ms (typ) / 8ms (max)
          ● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

          ● Voltage: 0.5-120V (phase)
          ● Current: 0.02-20×In
          ● Zero-Seq Current: 0.05-20A
          ● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

          ● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
          ● Frequency: ±0.01Hz
          ● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa

​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

Related products More
GWZC-9603 Reverse Power Protection Relay (ANSI 32)
GWZC-9603 Reverse Power Protection Relay
detail
GWZC-9601 Fault Islanding Protection Device
GWZC-9601 Fault Islanding Protection Device
detail
GWZC-9694 Low-Frequency Low-Voltage Load Shedding Device
GWZC-9694 Low-Frequency Low-Voltage Load Shedding Device
detail
GWZC-9581 Low-voltage generator protection relay
GWZC-9586 Low-voltage generator protection relay
detail
GWZC-9506 Cable insulation monitoring device (IMD)​​(ANSI 64)
GWZC-9506 Cable insulation monitoring device
detail
Technical Knowledge More
Ground Distance Protection (21G)
Differences Between Phase-to-Phase Distance Protection (21P) and Ground Distance Protection (21G)
The core difference between phase-to-phase distance protection and ground distance protection lies in the selection of measured quantities, fault response range, and connection methods. They complement each other to form a complete distance protection system for high-voltage transmission lines, both following the basic principle: operation if the measured impedance is less than the setting impedance.
2026/03/04
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
Transformer Protection Relay Panel
Transformer Protection Relay Panel:Composition and Function
Transformer Protection Relay Panel is primarily used in automation systems for substations and distribution stations in power systems of 11kV, 33kV, 132kV and above. Its main function is to ensure that the transformer can promptly trip the faulty circuit in case of overload, short circuit, gas relay activation, and other abnormal operating conditions, thereby protecting the main transformer from damage and preventing the expansion of faults.
2025/11/24
GWZC-9602 Anti-islanding protection relay
Anti-islanding protection relay Side View
Anti-islanding protection relay Rear View
Inquiry Consultation
产品表单
code img
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my