Back to smartelemfg Home
Contact us Merchants settle in
Back to smartelemfg Home
Home -Technical

Type Testing of Medium Voltage Switchgear According to IEC Standards

Source: Smartelecmfg 2025-09-22 17:21:24

          Type testing of medium voltage switchgear in accordance with IEC standards may involve two scenarios: First, testing at domestic accredited testing stations in compliance with the IEC 62271 series standards, resulting in test reports that conform to IEC 62271. Second, testing at international STL (Short-Circuit Testing Liaison) testing stations according to IEC standards and STL guidelines.

          For the same voltage level, frequency, and grounding method, IEC and GB standard tests are relatively similar. In fact, some parameters, such as power frequency withstand voltage, are even lower in IEC standards compared to GB standards.

          Domestic testing stations also conduct tests strictly in accordance with IEC standards, such as TRV parameters and test duties for short-circuit breaking tests of circuit breakers. Communication and logistics are generally more convenient, and international clients typically accept type test reports issued by Chinese testing stations with international laboratory mutual recognition marks. If certifications such as ASTA or TUV can be obtained through testing, the acceptance level abroad increases significantly, making the reports nearly as authoritative as those issued by international testing stations.

          Due to differences in rated voltage between IEC and GB standards, as well as the requirement for 60Hz frequency, testing according to IEC standard voltages such as 17.5kV at 60Hz can be challenging for domestic testing stations. The need for voltage adjustment, frequency conversion, and parameter modifications significantly extends the preparation time for tests, thereby increasing costs. For such specific IEC market requirements, testing at international stations like KEMA is more convenient, professional, and potentially even more cost-effective.

Temperature Rise Test
          In the IEC market, there is generally no requirement for a 1.1 times overload test. However, for 60Hz applications, the temperature rise is typically 1.05 times that of 50Hz. The test is generally stringent, with both sides of the switchgear tightly covered with 50mm thick foam boards. All other components must be sealed to simulate the actual operating conditions of the middle compartment accurately. Strict adherence to the requirement of busbars longer than 2 meters for incoming and outgoing connections is necessary. Temperature measurement points should be set according to standards, and there is generally no need to drill holes into solid-insulated poles to measure the temperature rise at lower connections.

Insulation Test
          Insulation tests are conducted based on standard atmospheric correction factors. Tests between phases and across breaks are performed according to standard requirements after applying the corrected parameters.

Dynamic and Thermal Withstand Tests
          At 60Hz, the peak withstand current is 2.6 times the short-time withstand current. For example, 31.5kA corresponds to 82kA. For grounding switches, the requirement is to ensure they can open immediately after the test. However, achieving immediate opening due to welding or thermal expansion can be challenging. Additionally, single-phase testing of the grounding circuit must be considered. For directly grounded neutral systems, the grounding switch must undergo testing under the most severe single-phase short-circuit current condition, typically for 1 second. In this case, the flexible connection of the grounding switch must withstand the short-circuit test, such as 31.5kA for 1 second. If the cross-sectional area is insufficient, it may burn out, leading to test failure.

Short-Circuit Breaking Test
          IEC 62271-100 does not include Test Duty 4 (electrical endurance) as specified in GB/T 1984, which requires full-capacity breaking for 30/50 operations. For IEC reports, tests must be conducted according to Test Duties 1–3 in the IEC standard, which involve different combinations of short-circuit breaking tests. Test Duty 1 requires 274 operations, while Test Duty 3 requires 72 operations. Since testing stations like KEMA charge based on working hours, the longer duration required for 274 operations results in higher costs.

          Additionally, if 60Hz is required, tests must be conducted according to 60Hz standards, such as using a first-pole-to-clear factor of 1.3. If both 50Hz and 60Hz compliance are required, tests must be performed according to the standards, such as conducting T60 and T100 tests at both frequencies.

Internal Arc Test
          The test sample must be rigorously inspected. For example, if there are ventilation covers, the test must be conducted with them open. If there are non-self-resetting covers, such as circuit breaker racking-in hole covers without spring reset mechanisms, the test must be performed with them open. Due to limited on-site testing conditions, it is recommended to test the switchgear together with its base frame domestically to avoid uneven mounting surfaces that could cause arcs to eject from the bottom and ignite indicators.

          International testing typically involves strict verification of the consistency between the sample and the design drawings, with measurements recorded and discrepancies documented and explained. If a test fails, it may be repeated after explaining the cause and obtaining approval. If design changes are made during retesting, other affected tests must be repeated. For example, if a grounding switch fails to open immediately after dynamic and thermal withstand tests and requires external force (e.g., a kick) to open, this will be documented in the report. To avoid such a statement, the design may be modified, such as changing the orientation of the grounding switch blade from downward to upward. However, this may necessitate retesting related mechanical operation and insulation tests. In unfortunate cases, such modifications may lead to failure in impulse withstand voltage tests, leaving no choice but to accept the report stating that external force is required for opening.

Product recommendations More
10-15KV Incoming Line Switchgear
detail
11kv Medium-Voltage Switchgear
detail
Marine Medium/High Voltage Switchboard
detail
FZN25-12 series load switchgear
detail
KYN61-40.5 withdrawable AC metal-enclosed high-voltage switchgear
detail
Technical More
PV-Grid-Connected-Cabinet
Composition and Functions of a 400V PV Low-Voltage Grid-Connection Cabinet
A 400V PV Low-Voltage Grid-Connection Cabinet is a critical interface device that connects the photovoltaic (PV) power generation system to the low-voltage grid. It is a dedicated distribution panel integrating protection, monitoring, metering, and control functions. It is primarily composed of the following core components:
2025/09/11
Switchgear
Selection Standards for Standard Parts in Switchgear
Switchgear requires the use of many fastening standard parts such as bolts, nuts, washers, and rivets. It is essential to select appropriate standard parts based on different applications to ensure functional requirements are met while enhancing product safety and cost-effectiveness.
2025/09/02
Marine Switchgear
Medium Voltage Marine Switchgear Solution
  Incoming Line Configuration: Marine switchgear systems are powered by multiple diesel generators operating in parallel. Each incoming line must be equipped with voltage transformers for accurate voltage measurement on the supply side.
2025/09/01
Medium-Voltage Switchgear
Medium-Voltage Switchgear Retrofit Solutions
   The typical service life of medium-voltage switchgear is approximately 20 years. After prolonged operation, various issues may arise, such as insulation aging, increased temperature rise, circuit breaker mechanism jamming, and loss of vacuum, all of which pose significant risks to continued operation. Replacing entire units requires substantial financial investment and time, whereas retrofitting offers a rapid solution to address safety hazards, revitalize the equipment, and ensure continued safe operation.
2025/09/01
Inquiry Consultation
+86-13655813785
+86-13655813785
+86-13655813785
+86-13655813785
home product email
live chat
my