difference between 3-way and 4-way rmu?

Source: Smartelecmfg 2025-06-19 16:35:35

        The difference between 3-way and 4-way Ring Main Units (RMUs) lies primarily in the number of cable compartments and the configuration of the internal busbar, which directly impact flexibility, reliability, and application. Here’s a breakdown:

Ring Main Unit

1.Number of Ways / Cable Compartments:
        3-Way RMU: Has three cable connection compartments.
        4-Way RMU: Has four cable connection compartments.

2.Busbar Configuration:
        3-Way RMU: Typically has a single, non-segmented busbar running through the unit. All three ways connect to this single busbar section.
        4-Way RMU: Includes an integrated bus-section switch or isolator. This splits the internal busbar into two separate sections (Section A and Section B). The fourth way is specifically for this bus-section switch/isolation function.

3.Functional Purpose & Flexibility:

1)3-Way RMU:
        Used for simple feeder connections.
        Common configurations: 1 Incomer (source) + 1 Outgoing Feeder + 1 Transformer Feeder OR 2 Outgoing Feeders + 1 Transformer Feeder.
        All loads/transformers are connected to the same single busbar section.
        Limitation: A fault on the busbar itself or the need for maintenance requires the entire RMU and all connected loads to be taken out of service.

2)4-Way RMU:
        The key feature is the bus-section switch/isolation function (the 4th way).
        his allows the busbar to be split into two independent sections (Section A and Section B).
        Enables connection of two independent incoming sources (e.g., two different feeders from the ring) – one to Section A, one to Section B.
        Outgoing feeders/transformers can then be connected to either Section A or Section B.

Critical Advantage: The bus-section switch allows:
        Isolation: One section (A or B) can be isolated for maintenance or repair while the other section remains live and supplies its connected loads.
        Fault Containment: A fault occurring on one busbar section (or a feeder connected to it) can be isolated, allowing the other section and its loads to remain operational.
        Source Redundancy: Enables true N-1 or similar redundancy schemes by feeding from two separate sources.

4.Reliability & Continuity of Supply:
        3-Way RMU: Offers lower reliability for the connected loads if the busbar fails or needs maintenance. All loads lose supply.
        4-Way RMU: Offers significantly higher reliability and continuity of supply. The ability to isolate half the busbar means only the loads on the faulted/maintenance section lose power, while the other half stays online.

5.Physical Size and Cost:
        3-Way RMU: More compact and generally less expensive due to fewer compartments and simpler busbar.
        4-Way RMU: Larger footprint (due to the extra compartment) and more expensive because of the added complexity of the bus-section switching/isolation mechanism.

6.Typical Applications:
        3-Way RMU: Ideal for smaller substations, branch points on the network, or supplying less critical loads where the cost/space saving is a priority and brief outages affecting all loads are acceptable for busbar work.
        4-Way RMU: Essential for critical substations, points where two feeders meet (like a true ring interconnection point), or feeding important loads requiring higher supply continuity. Used where network reliability standards demand busbar sectionalization.

difference between 3-way and 4-way rmu

In essence: The 4-way RMU adds the crucial bus-section switching capability that the 3-way lacks. This single feature provides significantly enhanced operational flexibility, fault management, and supply reliability, making it necessary for critical network nodes, albeit at a higher cost and size. The 3-way RMU is a simpler, more economical solution for less critical points in the distribution network.

 

Product recommendations More
Ring Main Unit (RMU)
detail
FZN25-12 series load switchgear
detail
KYN61-40.5 withdrawable AC metal-enclosed high-voltage switchgear
detail
XGN17-40.5 fixed-type high-voltage switchgear
detail
High Voltage Shore Connection Cabinet
detail
Technical More
Gas-Insulated Switchgear (GIS)
Gas-Insulated Switchgear (GIS) for High-Altitude Applications
For Gas-Insulated Switchgear (GIS), since the main live circuits are enclosed within sealed, gas-filled compartments and external connections utilize solid insulation, the insulation performance is unaffected by atmospheric pressure. The primary consideration for GIS at high altitudes is the mechanical strength of the gas enclosure (gas compartment).
2025/08/08
switchgear
What are the differences between IEC-standard switchgear and UL-standard switchgear?
IEC standard switchgear and UL standard switchgear (represented by UL1558 and UL891) fall under different technical systems in power systems, with differences mainly reflected in their standard frameworks, structural design, performance requirements, and applicable scenarios. The following is a comprehensive comparative analysis:
2025/08/08
Ring Main Unit
Technical Requirements and Specifications for 17.5kV Ring Main Units in the Saudi National Grid
SEC Specifications: 17.5kV Ring Main Unit (RMU) - Key Features         Outdoor Enclosure: Designed for outdoor installation.         Dedicated Cable Withstand Voltage Test Terminal Compartment: Features a separate, accessible compartment for cable high-potential (Hi-Pot) testing.         Self-Powered Protection Unit: Utilizes an internal power source for the protection relay.         SF6 Insulated, Single-Tank Design F+F+V Configuration: Common SF6 gas tank housing a combination of Load Switch (F) + Load Switch (F) + Circuit Breaker (V).         Ratings: Ring Switch Unit: 630A. Feeder Circuit Breaker: 200A.         Compliance Standard: SEC Standard 32-SDMS-11.
2025/08/08
Medium Voltage Switchgear
Medium Voltage Switchgear UL Standard Specifications
Switchgear destined for the North American market requires UL (Underwriters Laboratories) certification. UL is a U.S. safety certification organization. It develops its own standards, such as UL 891 (Dead-Front Distribution Switchboards), UL 67 (Panelboards), and UL 845 (Motor Control Centers), and also provides product certification services.
2025/08/07
Inquiry Consultation
+86-13655813785
+86-13655813785
+86-13655813785
+86-13655813785
home product email
live chat
my