difference between 3-way and 4-way rmu?

Source: Smartelecmfg 2025-06-19 16:35:35

        The difference between 3-way and 4-way Ring Main Units (RMUs) lies primarily in the number of cable compartments and the configuration of the internal busbar, which directly impact flexibility, reliability, and application. Here’s a breakdown:

Ring Main Unit

1.Number of Ways / Cable Compartments:
        3-Way RMU: Has three cable connection compartments.
        4-Way RMU: Has four cable connection compartments.

2.Busbar Configuration:
        3-Way RMU: Typically has a single, non-segmented busbar running through the unit. All three ways connect to this single busbar section.
        4-Way RMU: Includes an integrated bus-section switch or isolator. This splits the internal busbar into two separate sections (Section A and Section B). The fourth way is specifically for this bus-section switch/isolation function.

3.Functional Purpose & Flexibility:

1)3-Way RMU:
        Used for simple feeder connections.
        Common configurations: 1 Incomer (source) + 1 Outgoing Feeder + 1 Transformer Feeder OR 2 Outgoing Feeders + 1 Transformer Feeder.
        All loads/transformers are connected to the same single busbar section.
        Limitation: A fault on the busbar itself or the need for maintenance requires the entire RMU and all connected loads to be taken out of service.

2)4-Way RMU:
        The key feature is the bus-section switch/isolation function (the 4th way).
        his allows the busbar to be split into two independent sections (Section A and Section B).
        Enables connection of two independent incoming sources (e.g., two different feeders from the ring) – one to Section A, one to Section B.
        Outgoing feeders/transformers can then be connected to either Section A or Section B.

Critical Advantage: The bus-section switch allows:
        Isolation: One section (A or B) can be isolated for maintenance or repair while the other section remains live and supplies its connected loads.
        Fault Containment: A fault occurring on one busbar section (or a feeder connected to it) can be isolated, allowing the other section and its loads to remain operational.
        Source Redundancy: Enables true N-1 or similar redundancy schemes by feeding from two separate sources.

4.Reliability & Continuity of Supply:
        3-Way RMU: Offers lower reliability for the connected loads if the busbar fails or needs maintenance. All loads lose supply.
        4-Way RMU: Offers significantly higher reliability and continuity of supply. The ability to isolate half the busbar means only the loads on the faulted/maintenance section lose power, while the other half stays online.

5.Physical Size and Cost:
        3-Way RMU: More compact and generally less expensive due to fewer compartments and simpler busbar.
        4-Way RMU: Larger footprint (due to the extra compartment) and more expensive because of the added complexity of the bus-section switching/isolation mechanism.

6.Typical Applications:
        3-Way RMU: Ideal for smaller substations, branch points on the network, or supplying less critical loads where the cost/space saving is a priority and brief outages affecting all loads are acceptable for busbar work.
        4-Way RMU: Essential for critical substations, points where two feeders meet (like a true ring interconnection point), or feeding important loads requiring higher supply continuity. Used where network reliability standards demand busbar sectionalization.

difference between 3-way and 4-way rmu

In essence: The 4-way RMU adds the crucial bus-section switching capability that the 3-way lacks. This single feature provides significantly enhanced operational flexibility, fault management, and supply reliability, making it necessary for critical network nodes, albeit at a higher cost and size. The 3-way RMU is a simpler, more economical solution for less critical points in the distribution network.

 

Product recommendations More
Ring Main Unit (RMU)
detail
FZN25-12 series load switchgear
detail
KYN61-40.5 withdrawable AC metal-enclosed high-voltage switchgear
detail
XGN17-40.5 fixed-type high-voltage switchgear
detail
High Voltage Shore Connection Cabinet
detail
Technical More
Medium-Voltage-Switchgear
Type Testing of Medium Voltage Switchgear According to IEC Standards
Type testing of medium voltage switchgear in accordance with IEC standards may involve two scenarios: First, testing at domestic accredited testing stations in compliance with the IEC 62271 series standards, resulting in test reports that conform to IEC 62271. Second, testing at international STL (Short-Circuit Testing Liaison) testing stations according to IEC standards and STL guidelines.
2025/09/22
PV-Grid-Connected-Cabinet
Composition and Functions of a 400V PV Low-Voltage Grid-Connection Cabinet
A 400V PV Low-Voltage Grid-Connection Cabinet is a critical interface device that connects the photovoltaic (PV) power generation system to the low-voltage grid. It is a dedicated distribution panel integrating protection, monitoring, metering, and control functions. It is primarily composed of the following core components:
2025/09/11
Switchgear
Selection Standards for Standard Parts in Switchgear
Switchgear requires the use of many fastening standard parts such as bolts, nuts, washers, and rivets. It is essential to select appropriate standard parts based on different applications to ensure functional requirements are met while enhancing product safety and cost-effectiveness.
2025/09/02
Marine Switchgear
Medium Voltage Marine Switchgear Solution
  Incoming Line Configuration: Marine switchgear systems are powered by multiple diesel generators operating in parallel. Each incoming line must be equipped with voltage transformers for accurate voltage measurement on the supply side.
2025/09/01
Inquiry Consultation
+86-13655813785
+86-13655813785
+86-13655813785
+86-13655813785
home product email
live chat
my