GWZC-9828 Transformer Non-Electrical Protection Relay
Transformer Non-Electrical Protection Relay Side View
Transformer Non-Electrical Protection Relay Rear View
GWZC-9828 Transformer Non-Electrical Protection Relay
Transformer Non-Electrical Protection Relay Side View
Transformer Non-Electrical Protection Relay Rear View
GWZC-9828 Transformer Non-Electrical Protection Relay

Applicable Scope :The ​Transformer Non-Electrical Protection Relay​ monitors oil temperature, gas accumulation, pressure, and liquid levels in oil-immersed transformers (35kV+). Installed in control cabinets or directly on transformers (e.g., Buchholz relay), it provides alarms/trips to prevent insulation breakdown or overheating. Complementing electrical protection, it ensures reliability in substations, power plants, and industrial applications.

Product functions(ANSI):71G | 26/49 | 63 | 38

Communication functions :Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction :

          The ​Transformer Non-Electrical Protection Relay​ is designed to safeguard oil-immersed power transformers (35kV and above) by monitoring critical mechanical and thermal parameters such as gas accumulation (Buchholz protection), oil temperature, sudden pressure changes, and liquid levels. Typically installed either in control cabinets or directly on the transformer body (e.g., Buchholz relay on piping), it provides essential alarms and trip signals to prevent catastrophic failures caused by insulation breakdown, overheating, or internal faults.

          This Transformer Non-Electrical Protection Relay​ complements electrical relays (e.g., differential, overcurrent) to form a complete transformer protection scheme, making it indispensable in grid substations, power plants, and industrial applications where transformer reliability is critical.

Product functionsANSI):

1.Light Gas Protection (ANSI 71G)
2.Heavy Gas Protection (ANSI 71G)
3.High Oil Temperature Protection (ANSI 26/49)
4.Pressure Relief Protection (ANSI 63)
5.Cooler Failure Protection (ANSI 38)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

Related products More
GWZC-9887 Generator-Transformer Differential Protection Relay (87G|87T)
GWZC-9887 Generator-Transformer Differential Protection Relay
detail
GWZC-9621 Distribution transformer protection relay
GWZC-9621 Distribution transformer protection relay
detail
GWZC-9829 Main Transformer On-load Tap Changer Control Relay
GWZC-9829 Main Transformer On-load Tap Changer Control Relay
detail
GWZC-9827 Transformer Backup Protection Relay
GWZC-9827 Transformer Backup Protection Relay
detail
GWZC-9821C Transformer Differential Protection Relay (87H | 87 | 87AL)
GWZC-9821C Transformer Differential Protection Relay
detail
Technical Knowledge More
Automatic Transfer Switch (ATS) Side View
What is Parallel Operation
​Parallel operation​ involves connecting two or more independent AC power sources (e.g., generators, grids) to share electrical loads seamlessly. This process—synchronization—demands precise matching of voltage magnitude, frequency, and phase angles between systems before interconnection. Critical for grid expansion, backup power, and renewable integration, it enables redundant supply during failures.
2025/08/15
Generator-Transformer Differential Protection Relay Rear View
Ring-Closing Operation: Definition & Importance in Power Grids
A ring-closing operation involves closing a normally open switch within a closed-loop electrical network fed by a single power source. This creates parallel paths to redistribute loads without interruption, primarily for maintenance or network reconfiguration. Key prerequisites are voltage difference under 5%, phase angle alignment below 5 degrees, and pre-calculation of induced circulating currents to avoid equipment damage. Distinct from connecting independent systems, this procedure requires advanced monitoring but avoids synchronization complexity. Strict protocols using real-time sensors and simulations ensure safe execution, making it fundamental for resilient distribution networks like ring-main units (RMUs) in urban grids.
2025/08/14
Synchronism Check Function vs. Synchronizing Function: Roles, Differences, and Applications
This article compares the ​synchronism check function​ in line protection devices and the ​synchronizing function​ in dedicated synchronizing equipment. The ​synchronism check function​ serves as a safety interlock for circuit breaker closing operations, while the ​synchronizing function​ enables precise generator synchronization and critical tie-line interconnections with active parameter regulation. Explore core principles, application scenarios, and technical distinctions between these critical power system components.
2025/08/11
GWZC-9828 Transformer Non-Electrical Protection Relay
Transformer Non-Electrical Protection Relay Side View
Transformer Non-Electrical Protection Relay Rear View
Inquiry Consultation
产品表单
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my