GWZC-9828 Transformer Non-Electrical Protection Relay
Transformer Non-Electrical Protection Relay Side View
Transformer Non-Electrical Protection Relay Rear View
GWZC-9828 Transformer Non-Electrical Protection Relay
Transformer Non-Electrical Protection Relay Side View
Transformer Non-Electrical Protection Relay Rear View
GWZC-9693 Transformer Non-Electrical Protection Relay

Applicable Scope :The ​Transformer Non-Electrical Protection Relay​ monitors oil temperature, gas accumulation, pressure, and liquid levels in oil-immersed transformers (35kV+). Installed in control cabinets or directly on transformers (e.g., Buchholz relay), it provides alarms/trips to prevent insulation breakdown or overheating. Complementing electrical protection, it ensures reliability in substations, power plants, and industrial applications.

Product functions(ANSI):71G | 26/49 | 63 | 38

Communication functions :Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction :

          The ​Transformer Non-Electrical Protection Relay​ is designed to safeguard oil-immersed power transformers (35kV and above) by monitoring critical mechanical and thermal parameters such as gas accumulation (Buchholz protection), oil temperature, sudden pressure changes, and liquid levels. Typically installed either in control cabinets or directly on the transformer body (e.g., Buchholz relay on piping), it provides essential alarms and trip signals to prevent catastrophic failures caused by insulation breakdown, overheating, or internal faults.

          This Transformer Non-Electrical Protection Relay​ complements electrical relays (e.g., differential, overcurrent) to form a complete transformer protection scheme, making it indispensable in grid substations, power plants, and industrial applications where transformer reliability is critical.

Product functionsANSI):

1.Light Gas Protection (ANSI 71G)
2.Heavy Gas Protection (ANSI 71G)
3.High Oil Temperature Protection (ANSI 26/49)
4.Pressure Relief Protection (ANSI 63)
5.Cooler Failure Protection (ANSI 38)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

Related products More
GWZC-9000 Main Transformer Protection Panel
Main Transformer Protection Panel
detail
GWZC-9521 Distribution transformer protection relay
GWZC-9521 Distribution transformer protection relay
detail
GWZC-9621C Transformer Differential Protection Relay (87T)
GWZC-9621C Transformer Differential Protection Relay
detail
GWZC-9691 Main Transformer Differential Protection Relay(87T)
GWZC-9691 Main Transformer Differential Protection Relay
detail
GWZC-9694 Main Transformer On-load Tap Changer Control Relay
GWZC-9829 Main Transformer On-load Tap Changer Control Relay
detail
Technical Knowledge More
Ground Distance Protection (21G)
Differences Between Phase-to-Phase Distance Protection (21P) and Ground Distance Protection (21G)
The core difference between phase-to-phase distance protection and ground distance protection lies in the selection of measured quantities, fault response range, and connection methods. They complement each other to form a complete distance protection system for high-voltage transmission lines, both following the basic principle: operation if the measured impedance is less than the setting impedance.
2026/03/04
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
Transformer Protection Relay Panel
Transformer Protection Relay Panel:Composition and Function
Transformer Protection Relay Panel is primarily used in automation systems for substations and distribution stations in power systems of 11kV, 33kV, 132kV and above. Its main function is to ensure that the transformer can promptly trip the faulty circuit in case of overload, short circuit, gas relay activation, and other abnormal operating conditions, thereby protecting the main transformer from damage and preventing the expansion of faults.
2025/11/24
GWZC-9828 Transformer Non-Electrical Protection Relay
Transformer Non-Electrical Protection Relay Side View
Transformer Non-Electrical Protection Relay Rear View
Inquiry Consultation
产品表单
code img
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my