Distance protection relay Side View
Distance protection relay Rear View
GWZC-9812 Distance protection relay
Distance protection relay Side View
Distance protection relay Rear View
GWZC-9812 Distance protection relay(21 | 21G | 21FL)

Applicable Scope :The GWZC-9812 Distance Protection Relay is designed for comprehensive directional line protection, measurement, and control in electrical power systems with voltages below 35kV, specifically in non-directly grounded or resistance-grounded networks. This integrated device features core functions including distance, current, and voltage protection, as well as three-phase auto-reclosing as standard configurations.

Product functions(ANSI):21 | 21G | 21FL | 68 | 50/51 | 50N/51N | 32 | 27 | 79 | 50HS/79 | 49 | 81U | 60FL
Communication functions :  Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction  of Distance Protection Relay
          The GWZC-9812 Distance Protection Relay is designed for comprehensive directional line protection, measurement, and control in electrical power systems with voltages below 35kV, specifically in non-directly grounded or resistance-grounded networks. This integrated device features core functions including distance, current, and voltage protection, as well as three-phase auto-reclosing as standard configurations.

          The GWZC-9812 Distance Protection Relay is suitable for applications in substations, distribution stations, and industrial plants, providing reliable fault detection and system monitoring. The relay is typically installed locally in line switchgear cabinets for direct access or mounted in group panels within control rooms for centralized operations.

Product functions(ANSI)

1.​Phase Distance Protection (3-Zone) (ANSI 21)
2.​Ground Distance Protection (3-Zone) (ANSI 21G)
3.Fault Location (ANSI 21FL)
4.​Asymmetrical Successive Trip Protection (ANSI 68)
​5.​Double-Circuit Successive Trip Protection (ANSI 68)
6.Phase Overcurrent Protection (3-Zone) (ANSI 50/51)
7.​Zero-Sequence Overcurrent Protection (3-Zone) (ANSI 50N/51N)
​8.​Directional Blocking (ANSI 32)
​9.​Undervoltage Blocking (ANSI 27)
10.Automatic Reclosing (ANSI 79)
11.​​Reclosing Acceleration Protection (ANSI 50HS/79)
​12.​Overload Protection (ANSI 49)
​13.​Underfrequency Protection (ANSI 81U)
​14.Undervoltage Protection (ANSI 27)
15.PT Fuse Failure Detection (ANSI 60FL)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

 

Related products More
GWZC-9611 Feeder Protection Relay
GWZC-9611 Feeder Protection Relay
detail
GWZC-9913 FO Line Diff Relay(87L)
GWZC-9913 FO Line Diff Relay(87L)
detail
GWZC-9916 Bus differential protection relay
GWZC-9916 Bus differential protection relay
detail
GWZC-9811C Line differential protection relay (87H | 87)
GWZC-9811C Line differential protection relay
detail
GWZC-9811 Line protection relay
GWZC-9811  Line protection relay
detail
Technical Knowledge More
Automatic Transfer Switch (ATS) Side View
What is Parallel Operation
​Parallel operation​ involves connecting two or more independent AC power sources (e.g., generators, grids) to share electrical loads seamlessly. This process—synchronization—demands precise matching of voltage magnitude, frequency, and phase angles between systems before interconnection. Critical for grid expansion, backup power, and renewable integration, it enables redundant supply during failures.
2025/08/15
Generator-Transformer Differential Protection Relay Rear View
Ring-Closing Operation: Definition & Importance in Power Grids
A ring-closing operation involves closing a normally open switch within a closed-loop electrical network fed by a single power source. This creates parallel paths to redistribute loads without interruption, primarily for maintenance or network reconfiguration. Key prerequisites are voltage difference under 5%, phase angle alignment below 5 degrees, and pre-calculation of induced circulating currents to avoid equipment damage. Distinct from connecting independent systems, this procedure requires advanced monitoring but avoids synchronization complexity. Strict protocols using real-time sensors and simulations ensure safe execution, making it fundamental for resilient distribution networks like ring-main units (RMUs) in urban grids.
2025/08/14
Synchronism Check Function vs. Synchronizing Function: Roles, Differences, and Applications
This article compares the ​synchronism check function​ in line protection devices and the ​synchronizing function​ in dedicated synchronizing equipment. The ​synchronism check function​ serves as a safety interlock for circuit breaker closing operations, while the ​synchronizing function​ enables precise generator synchronization and critical tie-line interconnections with active parameter regulation. Explore core principles, application scenarios, and technical distinctions between these critical power system components.