GWZC-9812 Distance protection relay
Distance protection relay Side View
Distance protection relay Rear View
GWZC-9612 Distance protection relay(21 | 21G | 21FL)

Applicable Scope :The GWZC-9612 Distance Protection Relay is designed for comprehensive directional line protection, measurement, and control in electrical power systems with voltages below 35kV, specifically in non-directly grounded or resistance-grounded networks. This integrated device features core functions including distance, current, and voltage protection, as well as three-phase auto-reclosing as standard configurations.

Product functions(ANSI):21 | 21G | 21FL | 68 | 50/51 | 50N/51N | 32 | 27 | 79 | 50HS/79 | 49 | 81U | 60FL
Communication functions :  Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction  of Distance Protection Relay
          The GWZC-9612 Distance Protection Relay is designed for comprehensive directional line protection, measurement, and control in electrical power systems with voltages below 35kV, specifically in non-directly grounded or resistance-grounded networks. This integrated device features core functions including distance, current, and voltage protection, as well as three-phase auto-reclosing as standard configurations.

          The GWZC-9612 Distance Protection Relay is suitable for applications in substations, distribution stations, and industrial plants, providing reliable fault detection and system monitoring. The relay is typically installed locally in line switchgear cabinets for direct access or mounted in group panels within control rooms for centralized operations.

Product functions(ANSI)

1.​Phase Distance Protection (3-Zone) (ANSI 21)
2.​Ground Distance Protection (3-Zone) (ANSI 21G)
3.Fault Location (ANSI 21FL)
4.​Asymmetrical Successive Trip Protection (ANSI 68)
​5.​Double-Circuit Successive Trip Protection (ANSI 68)
6.Phase Overcurrent Protection (3-Zone) (ANSI 50/51)
7.​Zero-Sequence Overcurrent Protection (3-Zone) (ANSI 50N/51N)
​8.​Directional Blocking (ANSI 32)
​9.​Undervoltage Blocking (ANSI 27)
10.Automatic Reclosing (ANSI 79)
11.​​Reclosing Acceleration Protection (ANSI 50HS/79)
​12.​Overload Protection (ANSI 49)
​13.​Underfrequency Protection (ANSI 81U)
​14.Undervoltage Protection (ANSI 27)
15.PT Fuse Failure Detection (ANSI 60FL)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

 

Related products More
GWZC-9614 Bus differential protection relay
GWZC-9614Bus differential protection relay
detail
GWZC-9611C Line differential protection relay (87H | 87)
GWZC-9611C Line differential protection relay
detail
GWZC-9611 Line protection relay
GWZC-9611  Line protection relay
detail
GWZC-9511 Feeder Protection Relay
GWZC-9511 Feeder Protection Relay
detail
GWZC-9613 FO Line Diff Relay(87L)
GWZC-9613 FO Line Diff Relay(87L)
detail
Technical Knowledge More
Transformer Protection Relay Panel
Renovation Scheme for Unattended Automatic System of Hydropower Station
The core of the transformation of the unattended automation system for hydropower stations is to upgrade the traditional manually attended power station into a modern intelligent power station with "unattended operation and minimal personnel on duty" through computerized monitoring, intelligent sensing, reliable communication and remote centralized control. It realizes remote monitoring, automatic control, fault self-diagnosis and safety early warning, greatly reducing labor costs and improving operational efficiency and safety. Among them, the secondary electrical system, as the "nervous system, brain and safety line of defense" of the power station, is the core support for the unattended transformation. Without a reliable secondary system, true unattended operation cannot be achieved. Therefore, this integration will focus on improving the detailed content of secondary electrical equipment while retaining the full process details of the transformation.
2026/04/21
Ground Distance Protection (21G)
Differences Between Phase-to-Phase Distance Protection (21P) and Ground Distance Protection (21G)
The core difference between phase-to-phase distance protection and ground distance protection lies in the selection of measured quantities, fault response range, and connection methods. They complement each other to form a complete distance protection system for high-voltage transmission lines, both following the basic principle: operation if the measured impedance is less than the setting impedance.
2026/03/04
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
GWZC-9812 Distance protection relay
Distance protection relay Side View
Distance protection relay Rear View
Inquiry Consultation
产品表单
code img
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my