GWZC-9601 Fault Islanding Protection Device
Fault Islanding Protection Device Side View
Fault Islanding Protection Device Rear View
GWZC-9601 Fault Islanding Protection Device
Fault Islanding Protection Device Side View
Fault Islanding Protection Device Rear View
GWZC-9601 Fault Islanding Protection Device

Applicable Scope :The ​GWZC-9601 Fault Disconnection Relay​ provides protection for ​10kV-35kV distribution networks, ​microgrids, and ​renewable energy systems​ by detecting and isolating faults (overcurrent, under-voltage, frequency deviations) to prevent cascading failures. Installed in ​substation switchgear​ or ​grid interconnection points, it enables selective fault isolation while maintaining power supply stability.

Product functions(ANSI):59N | 27 | 59 | 81U | 81O | 78 | 60 | 94

Communication functions :Supported Protocols :​​ IEC 60870-5-103 (over Ethernet) | MODBUS RTU (via RS-485) | IEC 61850 (Ed.2 or Ed.1, as applicable)
​Interfaces:​​2× Ethernet Ports​ (IEEE 802.3 compliant, 10/100 Mbps) | 2× RS-485 Ports​ (ANSI/TIA-485-A standard, galvanically isolated)

Other functions : Support time synchronization via communication message, SNTP (Simple Network Time Protocol) time synchronization, and IRIG-B time synchronization. Support the dot matrix printing function with serial port communication. Support the fault recording function

Product Introduction Technical Parameter Size

Product Introduction :

          The ​GWZC-9601 Fault Disconnection Relay​ is a specialized protection device designed for ​10kV–35kV distribution networks, ​renewable energy integration points, and ​microgrid systems, where rapid fault isolation is critical to prevent cascading failures and maintain grid stability. It detects and isolates faults (such as overcurrent, under-voltage, or frequency deviations) while supporting automatic or manual system separation to protect critical loads.

          The ​GWZC-9601 Fault Disconnection Relay Typically installed in ​distribution substation switchgear cabinets​ or at ​tie points between grid sections, this relay ensures selective fault isolation while preserving power supply continuity in unaffected areas.

Product functionsANSI):

1.Two-stage Zero-sequence Overvoltage Islanding (ANSI 59N)
2.Two-stage Undervoltage Islanding (ANSI 27)
3.Two-stage Bus Overvoltage Islanding (ANSI 59)
4.Two-stage Underfrequency Islanding (ANSI 81U)
5.Two-stage Overfrequency Islanding (ANSI 81O)
6.Out-of-step Islanding (ANSI 78)
7.Potential Transformer Fuse Failure (ANSI 60)
8.External Trip 1/2 (ANSI 94)

Electrical Specifications​

​Power Supply:​​

● AC: 85-264V, 47-63Hz (≤15% THD)
● DC: 100-370V (≤5% ripple)

​Rated AC Parameters:​​

● Voltage: 100V/√3 or 100V
● Current: 5A/1A
● Frequency: 50Hz

​Overload Capacity:​​

● Current Circuit: 2×In continuous | 10×In (10s) | 40×In (1s)
● Voltage Circuit: 1.5×Un continuous

​Power Consumption:​​

● Supply: <10W (static), ≤15W (trip)
● Current Circuit: ≤1VA/phase (5A) / ≤0.5VA/phase (1A)
● Voltage Circuit: ≤0.5VA/phase

​Digital Output:​​

● Dry contact (8A@250VAC / 30VDC)
● Dielectric: 4kVAC (coil-contact), 1kVAC (open contact)
● Operating Time: 5ms (typ) / 8ms (max)
● Mechanical Life: 100k operations

​Protection Performance​

​Operating Range:​​

● Voltage: 0.5-120V (phase)
● Current: 0.02-20×In
● Zero-Seq Current: 0.05-20A
● Frequency: 35-65Hz | Delay: 0-100s

​Accuracy:​​

● Voltage/Current: ±2.5% or ±0.1V/±0.05A (whichever greater)
● Frequency: ±0.01Hz
● Settings: ±2.5%

​Trip Time:​​

● Instantaneous: ≤35ms (≥1.2× setting)
● Time-Delayed: ≤1% of setting or 35ms

​Measurement & Monitoring​

​Range:​​

● Voltage: 0.5-120V | Current: 0.02-1.2×In

​Accuracy:​​

● V/I: ±0.2% | Frequency: ±0.01Hz | Other: 0.5%
● Time Sync: ≤2ms | SOE: ≤1ms

​Event Recording:​​

● 128 protection trips/operations
● 32 self-tests/fault waveforms (COMTRADE)

​Environmental & Mechanical​

​Operating Temp:​​

● Standard: -10°C to +55°C
● Extended: -40°C to +70°C*

​Storage Temp:​​ -40°C to +80°C
​Humidity:​​ 5-90% RH (non-condensing)
​Pressure:​​ 60-110 kPa
​Compliance:​​

● IEC 60255-21 (vibration/shock)
● IEC 61000-6 (EMC)

Related products More
GWZC-9602 Anti-islanding protection relay(AIP)
GWZC-9602 Anti-islanding protection relay
detail
GWZC-9603 Reverse Power Protection Relay (ANSI 32)
GWZC-9603 Reverse Power Protection Relay
detail
GWZC-9694 Low-Frequency Low-Voltage Load Shedding Device
GWZC-9694 Low-Frequency Low-Voltage Load Shedding Device
detail
GWZC-9581 Low-voltage generator protection relay
GWZC-9586 Low-voltage generator protection relay
detail
GWZC-9506 Cable insulation monitoring device (IMD)​​(ANSI 64)
GWZC-9506 Cable insulation monitoring device
detail
Technical Knowledge More
Ground Distance Protection (21G)
Differences Between Phase-to-Phase Distance Protection (21P) and Ground Distance Protection (21G)
The core difference between phase-to-phase distance protection and ground distance protection lies in the selection of measured quantities, fault response range, and connection methods. They complement each other to form a complete distance protection system for high-voltage transmission lines, both following the basic principle: operation if the measured impedance is less than the setting impedance.
2026/03/04
Generator Protection Panel
Generator Protection Relay Panel : Composition and Function
Integrating protection, measurement, and communication, the Generator Protection Relay Panel can realize the protection and control of various units, enabling unattended or minimally attended operation. It can achieve generator differential protection, rotor earth fault protection, stator earth fault protection, excitation protection, overcurrent protection, overvoltage protection, overload protection, backup protection, etc.
2025/11/25
Transformer Protection Relay Panel
Transformer Protection Relay Panel:Composition and Function
Transformer Protection Relay Panel is primarily used in automation systems for substations and distribution stations in power systems of 11kV, 33kV, 132kV and above. Its main function is to ensure that the transformer can promptly trip the faulty circuit in case of overload, short circuit, gas relay activation, and other abnormal operating conditions, thereby protecting the main transformer from damage and preventing the expansion of faults.
2025/11/24
GWZC-9601 Fault Islanding Protection Device
Fault Islanding Protection Device Side View
Fault Islanding Protection Device Rear View
Inquiry Consultation
产品表单
code img
Inquiry Consultation
+86-17621210051
+86-17621210051
+86-17621210051
+86-17621210051
home product email
live chat
my